Skip to main content
Siemens 6ES7134-4FB00-0AB0 — Analog Input Modules

Siemens 6ES7134-4FB00-0AB0 Analog Input Module, 2 AI, ±10 V

MPN6ES7134-4FB00-0AB0

Siemens ET 200S analog input module · 6ES7134-4FB00-0AB0 · 2 AI, ±5 V / 1-5 V / ±10 V · integrating measurement · wire-break diagnostics (1-5 V) · 15 mm wide · current production.

$90.30 – $183.00Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6ES7134-4FB00-0AB0 — Inputs & Signal Ranges
ParameterValue
Number of analog inputs2
Input range: -10 to +10 VYes
Input range: -5 to +5 VYes
Permissible input voltage, max. (destruction limit)35 V; 35 V continuous; 75 V for max. 1 ms (mark to space ratio 1:20)
Max. shielded signal cable length200 m
6ES7134-4FB00-0AB0 — Measurement Performance
ParameterValue
Resolution (bit incl. sign), max.14 bit; ±10 V: 13 bit + sign, ±5 V: 13 bit + sign; 1 to 5 V: 13 bit
Measurement principleintegrating
Voltage measurement error (±)0.4 %
Interference voltage suppression (at interference frequency)50 / 60 Hz
6ES7134-4FB00-0AB0 — Diagnostics & Monitoring
ParameterValue
Wire-break detectionYes; Measuring range 1 to 5 V only
6ES7134-4FB00-0AB0 — Isolation
ParameterValue
Isolation: channels to backplane busYes
Isolation: between channelsNo
Isolation test voltage500 V DC
6ES7134-4FB00-0AB0 — Power
ParameterValue
Rated value (DC)24 V; From power module
Power loss, typ.0.6 W
Reverse polarity protectionYes
6ES7134-4FB00-0AB0 — Mechanical
ParameterValue
Width15 mm
Height81 mm
Depth52 mm
Weight, approx.40 g

Product details

The 6ES7134-4FB00-0AB0 is a Siemens ET 200S 2-channel analog input module for voltage signals. It measures ±5 V, 1 to 5 V, or ±10 V using an integrating measurement principle, and each channel is parameterizable for digital filtering in four stages. Rated voltage of 24 V DC is supplied from the backplane bus; power loss is 0.6 W typical. The module is 15 mm wide, 81 mm high, and 52 mm deep, fitting a single ET 200S slot. Conversion time per channel is 65 ms (55/65 ms variants), and integration time is parameterizable at 16,7 or 20 ms. Isolation is tested at 500 V DC between channels and backplane bus.

Signal integrity and diagnostics

For clean signals in a noisy plant, each channel requires shielded cable; maximum cable run is 200 m. Wire-break detection is enabled only in the 1 to 5 V range. Group diagnostics (SF red LED) and per-channel overflow/underflow can be enabled or disabled. No isochronous mode (no equidistant cycle), so the module suits standard ET 200S applications rather than synchronized motion.

Frequently asked questions

What are the key specifications of this module?

It has 2 analog inputs for voltage ranges ±5 V / 1-5 V / ±10 V, integrating measurement, conversion time 65 ms per channel, wire-break diagnostics on 1-5 V range, power loss 0.6 W, dimensions 15 x 81 x 52 mm, and fits ET 200S distributed I/O.

What is the maximum cable length for this analog input module?

Shielded cable can be run up to 200 m per channel.

MPN
6ES7134-4FB00-0AB0