Skip to main content
Siemens 6ES7134-4FB51-0AB0 — PLC I/O & Expansion Modules

Siemens 6ES7134-4FB51-0AB0 SIMATIC ET 200SP AI 2xU, 52 mm

MPN6ES7134-4FB51-0AB0

Siemens SIMATIC ET 200SP, analog input module, 6ES7134-4FB51-0AB0, 2 AI, ±10 V / ±5 V / ±2.5 V / 1-5 V, 52 mm depth.

$306.32 – $428.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7134-4FB51-0AB0 — I/O
ParameterValue
Analog inputs2
6ES7134-4FB51-0AB0 — Electrical
ParameterValue
Rated value (DC)24 V; From power module
Power loss (typ.)0.8 W
Current consumption from load voltage L+ (no load), max.35 mA
Reverse polarity protectionYes
Isolation test voltage500 V DC
Isolation: between channelsNo
Isolation: channels to backplane busYes
Max. cable length, shielded200 m
6ES7134-4FB51-0AB0 — Performance
ParameterValue
Resolution incl. overrange (bit, with sign), max.14 bit; ±10 V: 13 bit + sign, ±5 V: 13 bit + sign, ±2.5 V: 13 bit + sign; 1 to 5 V: 13 bit
ParameterizableYes; In four stages by means of digital filtering
Group fault indicator (SF, red LED)Yes
6ES7134-4FB51-0AB0 — Mechanical
ParameterValue
Height81 mm
Width15 mm
Depth52 mm
Weight (approx.)40 g

Product details

Analog input slice for the ET 200SP

The 6ES7134-4FB51-0AB0: 2-channel analog input module for the ET 200SP system. Captures voltage signals from ±10 V down to 1–5 V at 0.1 ms conversion time per channel. Cycle time for all channels max 1 ms, with isochronous mode for synchronized acquisition.

Parameterizable digital filtering

Filter set to one of four stages — none (1× cycle time), low (64×), medium (128×), high (512×). Low or high delay trades noise rejection against response time. For steady-state signals (e.g., temperature, level), medium or high filtering cleans up the acquired value. For transient capture or fast control loops, low or none preserves the edge.

Diagnostics and interrupt capability

Group diagnostics (SF red LED) can be enabled or disabled per channel. Hardware interrupt is parameterizable, as is overflow/underflow detection. Reverse polarity protection on the supply, and isolation tested at 500 V DC.

Frequently asked questions

What is the conversion time per channel?

0.1 ms per channel; cycle time for all channels max 1 ms.

MPN
6ES7134-4FB51-0AB0