Siemens 6ES7134-6JD00-0DA1 — Analog Input Modules

Siemens 6ES7134-6JD00-0DA1 Analog Input Module, 16-bit

MPN6ES7134-6JD00-0DA1
Active

Siemens SIMATIC ET 200SP, 6ES7134-6JD00-0DA1, Analog Input Module, 4 AI, 4- or 2-wire, thermocouple/mV, 16-bit, MSI Yes.

$175.26 – $521.27Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7134-6JD00-0DA1 — Inputs & Signal Ranges
ParameterValue
Number of analog inputs4
Input range: -80 to +80 mVYes; 16 bit incl. sign
Permissible input voltage, max. (destruction limit)30 V
Max. shielded signal cable length200 m; 100 m for thermocouples
6ES7134-6JD00-0DA1 — Measurement Performance
ParameterValue
Resolution (bit incl. sign), max.16 bit
Measurement principleintegrating (Sigma-Delta)
Temperature measurement error (±)0.005 %/K
Voltage measurement error (±)0.05 %; 0.2 % when SFU OFF
Interference voltage suppression (at interference frequency)16.6 / 50 / 60 Hz / off
Common-mode interference suppression, min.90 dB
Common-mode voltage, max.60 V; DC
6ES7134-6JD00-0DA1 — Diagnostics & Monitoring
ParameterValue
Wire-break detectionYes; channel by channel
Diagnostic alarmYes
Diagnostics functionYes
Limit value alarmYes; two upper and two lower limit values in each case
Supply voltage monitoringYes
6ES7134-6JD00-0DA1 — Isolation
ParameterValue
Isolation: channels to backplane busYes
Isolation: between channelsNo
Isolation test voltage707 V DC (type test)
6ES7134-6JD00-0DA1 — Power
ParameterValue
Rated value (DC)24 V
Power loss, typ.0.9 W
Reverse polarity protectionYes
6ES7134-6JD00-0DA1 — Environmental
ParameterValue
Operating temperature, horizontal mounting, max.60 °C
Operating temperature, horizontal mounting, min.-30 °C; < 0 °C as of FS02
Operating temperature, vertical mounting, max.50 °C
Operating temperature, vertical mounting, min.-30 °C; < 0 °C as of FS02
6ES7134-6JD00-0DA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight, approx.33 g

Product details

Wiring and integration

The 6ES7134-6JD00-0DA1: Parameterizable wire-break detection per channel and group error alarm are built in. Diagnostic alarm and limit value alarm (two upper, two lower) are configurable. I&M data from I&M0 to I&M3 is supported for asset management.

Frequently asked questions

What thermocouple types does this module support?

It supports types B, C, E, J, K, L, N, R, S, T, and U, all at 16-bit resolution including sign.

What is the maximum cable length for thermocouple inputs?

For thermocouples, shielded cable is limited to 100 m; for other signals it can be up to 200 m.

MPN
6ES7134-6JD00-0DA1