Siemens 6ES7134-6PA00-0BD0 — Analog Input Modules

Siemens 6ES7134-6PA00-0BD0 AI Energy, 20mm

MPN6ES7134-6PA00-0BD0

Siemens ET 200SP analog input module for energy measurement, 20 mm, 100-240 V AC, BU type D0.

$240.03 – $386.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7134-6PA00-0BD0 — Diagnostics & Monitoring
ParameterValue
Diagnostic alarmYes
Limit value alarmNo
6ES7134-6PA00-0BD0 — Isolation
ParameterValue
Isolation: channels to backplane busYes; 3 700V AC (type test) CAT III
Isolation test voltage2 300V AC for 1 min. (type test)
6ES7134-6PA00-0BD0 — Power
ParameterValue
Power loss, typ.0.6 W
6ES7134-6PA00-0BD0 — Environmental
ParameterValue
Operating temperature, horizontal mounting, max.60 °C
Operating temperature, horizontal mounting, min.0 °C
Operating temperature, vertical mounting, max.50 °C
Operating temperature, vertical mounting, min.0 °C
6ES7134-6PA00-0BD0 — Mechanical
ParameterValue
Width20 mm
Height73 mm
Depth58 mm
Weight, approx.45 g

Product details

The Siemens 6ES7134-6PA00-0BD0 is an ET 200SP analog input module dedicated to energy measurement — voltage, current, active/reactive power, and energy in a single 20 mm slice. It feeds on 100-240 V AC directly from the measured line (L1), eliminating a separate power supply. Mounted on a BU type D0 base unit, it fits any ET 200SP station.

What it measures and how you set it up

This module handles sinusoidal or distorted voltage curves and accepts current via an external CT (0.5 A secondary). It reports active power, reactive power, energy, frequency, and voltage — all cyclically and acyclically. Zero-point suppression is parameterizable from 20 to 250 mA (default 50 mA), useful for ignoring idle current on lightly loaded feeders. Firmware V2.0 supports I&M data records 0 through 3. Diagnostic alarms come standard; the green/red DIAG LED and red Fn LED per channel give quick fault isolation. No hardware interrupt or isochronous mode, but for standard sub-second energy monitoring that's not a gap. Mechanical coding on the module prevents plugging into the wrong base unit.

Frequently asked questions

What base unit does this module require?

It requires a BU type D0 base unit, such as the 6ES7193-4CC30-0AA0.

Does it measure active and reactive power?

Yes, it measures active power, reactive power, and energy, along with voltage, current, and frequency.

What is the module's supply voltage?

It is powered directly from the measured voltage circuit: 100-240 V AC via the L1 channel.

MPN