Skip to main content
Siemens 6ES7134-6PA21-0CU0 — Analog Input Modules

Siemens 6ES7134-6PA21-0CU0 ET 200SP Module, 24 V DC, 20 mm

MPN6ES7134-6PA21-0CU0
Active

Siemens SIMATIC ET 200SP analog input / energy measurement module, 6ES7134-6PA21-0CU0, 24 V DC supply, 58×20×73 mm, firmware V8.0.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7134-6PA21-0CU0 — Inputs & Signal Ranges
ParameterValue
Max. shielded signal cable length200 m
6ES7134-6PA21-0CU0 — Diagnostics & Monitoring
ParameterValue
Diagnostic alarmYes
Limit value alarmYes
6ES7134-6PA21-0CU0 — Isolation
ParameterValue
Isolation: channels to backplane busYes
Isolation: between channelsNo
Isolation test voltageBetween channels and backplane bus, 24 V supply: Routine test, 1 920 V AC, 2 s; between backplane bus and 24 V supply: Type test, 707 V DC
6ES7134-6PA21-0CU0 — Power
ParameterValue
Rated value (DC)24 V
Power loss, typ.400 mW; 3x 230 V AC
6ES7134-6PA21-0CU0 — Environmental
ParameterValue
Operating temperature, horizontal mounting, max.60 °C
Operating temperature, horizontal mounting, min.-30 °C
Operating temperature, vertical mounting, max.50 °C
Operating temperature, vertical mounting, min.-30 °C
6ES7134-6PA21-0CU0 — Mechanical
ParameterValue
Width20 mm
Height73 mm
Depth58 mm
Weight, approx.45 g

Product details

Integrator Field Note

The 6ES7134-6PA21-0CU0 is an ET 200SP energy measurement module that sits on a BU type U0 base unit. It measures current (up to 4 channels) and voltage, calculates power and energy, and flags limit-value alarms or hardware interrupts on up to 16 selectable process values. Supply is 24 V DC from the backplane; no external power needed. Firmware is V8.0 out of the box, and the module supports I&M data (I&M0–I&M3) plus online firmware update.

Mechanical Fit & Integration

Width 20 mm, depth 58 mm, height 73 mm — occupies a single ET 200SP slot. It requires a BU type U0 base unit (order separately). Shielded or unshielded cable runs up to 200 m per channel. Input resistance is 120 kΩ; power loss typ. 400 mW at 230 V AC.

Diagnostics & Commissioning

Standard diagnostics include line quality analysis, voltage swell/dip detection, overflow/underflow, and overload current monitoring. A diagnostic alarm or hardware interrupt can be assigned to any of 16 process thresholds. Automatic encoding means the module self-identifies on the backplane — no DIP-switch mapping. For FAT/SAT, the parameter length is 128 bytes and the I&M data helps track module history.

Frequently asked questions

What are the key dimensions of this module?

Width 20 mm, depth 58 mm, height 73 mm. It fits a standard ET 200SP slot with BU type U0 base unit.

MPN
6ES7134-6PA21-0CU0