Skip to main content
Siemens 6ES7142-6BG00-0BB0 — PLC Communication Modules

Siemens 6ES7142-6BG00-0BB0 SIMATIC ET 200SP DQ, 2x M12, IRT

MPN6ES7142-6BG00-0BB0
Active

Siemens SIMATIC ET 200SP, 6ES7142-6BG00-0BB0, PROFINET DQ module, 2x M12, IRT 250 µs, -40 to +60°C.

$583.20Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7142-6BG00-0BB0 — Identification
ParameterValue
Configurable from STEP 7 TIA Portal versionSTEP 7 V17 or higher with HSP 0363
Firmware versionV5.1.x
Hardware functional status (FS)FS02
6ES7142-6BG00-0BB0 — Communication
ParameterValue
Transmission rate, max.100 Mbit/s
TCP/IP supportYes; (only EtherNet/IP or Modbus TCP)
I&M data supportYes; I&M0 to I&M3
Isochronous modeYes
6ES7142-6BG00-0BB0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)20.4 V
Power loss (typ.)7 W
Reverse polarity protectionYes; against destruction; load increasing
Short-circuit protectionYes; per channel, electronic
6ES7142-6BG00-0BB0 — I/O
ParameterValue
Input data area1 byte for QI information
Output data area1 byte
6ES7142-6BG00-0BB0 — Environmental
ParameterValue
Operating temperature, max.60 °C
Operating temperature, min.-40 °C
IP protection degreeIP65/67/69K
6ES7142-6BG00-0BB0 — Mechanical
ParameterValue
Width45 mm
Height200 mm
Depth48 mm

Product details

The Siemens 6ES7142-6BG00-0BB0 is a digital output (DQ) module in the ET 200SP family, built for PROFINET with IRT down to 250 µs in 125 µs increments. That makes it a candidate for isochronous applications like motion or high-speed gating where jitter under 10 µs matters. It carries 1 byte of output data and reads 1 byte of QI information. Protocol support covers PROFINET, Modbus TCP, and EtherNet/IP. MRP and shared-device mode with up to two EtherNet/IP scanners allow it to sit in a redundant network without a separate media converter.

Protection and diagnostics that keep the line running

Each output channel is short-circuit protected to M with channel-by-channel detection. Wire-break detection is built in; it trips between 48 Ω and 4 kΩ. That gives the maintenance planner a reason to log the fault before the motor drops out. Temperature range covers -40 to +60 °C—no derating worry in an unheated enclosure or next to a hot machine base. Diagnostic LEDs (IO LED red-green-yellow, MS/NS green/red, RUN green, ERROR red, MAINT yellow) make first-line troubleshooting possible without a laptop.

No PROFIsafe or CIP Safety onboard—if the application needs functional safety over PROFINET, this module handles only standard I/O. The safety CPU would need a separate F-module.

Frequently asked questions

Does the 6ES7142-6BG00-0BB0 support isochronous real-time (IRT)?

Yes. IRT update times range from 250 µs to 4 ms in 125 µs steps, with jitter limited to 10 µs. That suits motion axes or high-speed crosscut applications.

Can it be used with Siemens S7-1500R/H or S7-400H redundant systems?

Yes. The module is explicitly approved for both S7-1500R/H and S7-400H redundant CPU architectures.

What diagnostics are available per channel?

Short-circuit protection per channel to M and wire-break detection with limits of 48 Ω to 4 kΩ. Status LEDs include IO, MS, NS, RUN, ERROR, and MAINT.

MPN
6ES7142-6BG00-0BB0