Siemens 6ES7148-6JE00-0BB0 — PLC Communication Modules

Siemens 6ES7148-6JE00-0BB0 IO-Link Master, 2x M12, -40-60°C

MPN6ES7148-6JE00-0BB0
Active

Siemens ET 200SP CM IO-Link master module, 6ES7148-6JE00-0BB0, with 2x M12 D-coded ports, DI per channel, DQ max 100 mA, IRT, -40 to 60 °C.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7148-6JE00-0BB0 — Identification
ParameterValue
Configurable from STEP 7 TIA Portal versionSTEP 7 V17 or higher with HSP 0378
Firmware versionV5.1.x
Hardware functional status (FS)FS01
6ES7148-6JE00-0BB0 — Communication
ParameterValue
Transmission rate, max.100 Mbit/s
TCP/IP supportYes; (only EtherNet/IP or Modbus TCP)
I&M data supportYes; I&M0 to I&M3
Isochronous modeNo
6ES7148-6JE00-0BB0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)20.4 V
Power loss (typ.)9.7 W
Reverse polarity protectionYes; against destruction
Short-circuit protectionYes; per channel, electronic
6ES7148-6JE00-0BB0 — I/O
ParameterValue
Input data area146 byte; + 8 bytes for QI information
Output data area130 byte
6ES7148-6JE00-0BB0 — Environmental
ParameterValue
Operating temperature, max.60 °C
Operating temperature, min.-40 °C
IP protection degreeIP65/67/69K
6ES7148-6JE00-0BB0 — Mechanical
ParameterValue
Width45 mm
Height200 mm
Depth48 mm

Product details

The Siemens 6ES7148-6JE00-0BB0 is an ET 200SP Communication Module for IO-Link, fitted with two M12, 4-pin D-coded ports. It provides one digital input per channel and a digital output rated at max 100 mA per channel, covering standard sensor and small actuator connectivity. IRT is supported in the 250 µs to 4 ms range, with a 125 µs frame, making it suitable for coordinated motion or fast loop applications. MRP, MSI, and MSO are all present, so the module fits into redundant ring topologies.

Sourcing and fit for your BOM line

This module is quoted to order. The input data length is 146 bytes plus 8 bytes for QI information; outputs occupy 130 bytes. That gives the planning engineer the IO map they need to size the process image. Wire-break detection is built into the digital inputs, triggering when input current drops below 0.3 mA per channel. The module supports I&M data up to I&M3, which helps with asset tracking and device replacement without reconfiguration.

Frequently asked questions

Will the 6ES7148-6JE00-0BB0 drop in for a 6ES7148-4FA00-0AB0?

No. The 6ES7148-6JE00-0BB0 is an ET 200SP module with a 45 mm width and backplane bus; the 4FA00-0AB0 is an ET 200S module with a different form factor. Panel wiring and mounting rail differ.

What is the digital output current rating?

The digital outputs are rated at max 100 mA per channel.

Does it support IO-Link?

Yes. It is an IO-Link master module with two M12, 4-pin D-coded ports.

MPN