6ES7193-6AP20-0AA0 — Identification
ParameterValue
Hardware functional status (FS)from FS04
6ES7193-6AP20-0AA0 — Environmental
ParameterValue
Operating temperature, horizontal install, min.-25 °C
Operating temperature, horizontal install, max.60 °C
Operating temperature, vertical install, max.50 °C
Operating temperature, vertical install, min.-25 °C
6ES7193-6AP20-0AA0 — Mechanical
ParameterValue
Width20 mm
Height69.5 mm
Depth59 mm
6ES7193-6AP20-0AA0 — Other specifications
ParameterValue
PCF100 m
PCF-GI250 m
Cu conductors100 m
Weight, approx.50 g
Plastic FOC50 m
Number of RJ45 ports1
Number of SCRJ ports1
Number of PROFINET interfaces1; 2 ports (SCRJ + RJ45)
Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual

Product details

The 6ES7193-6AP20-0AA0: SIMATIC ET 200SP BusAdapter BA SCRJ/RJ45 — a media converter that bridges plastic optical fiber (POF) and copper twisted-pair segments on a PROFINET line. One SCRJ fiber port plus one RJ45 port, both on a single PROFINET interface. PCF distance over standard POF is rated at 100 m; with graded-index (GI) fiber that extends to 250 m. Copper segment length is limited to 100 m, as typical for Ethernet. Active lifecycle status — no end-of-life notice on record.

Frequently asked questions

What fiber distances does this BusAdapter support?

Plastic optical fiber (POF) is rated to 100 m. Graded-index plastic fiber (PCF-GI) reaches 250 m. Copper (CAT cable) is limited to 100 m per standard Ethernet segment rules.

Does the 6ES7193-6AP20-0AA0 support PROFINET IRT?

The evidence does not list IRT explicitly, but the part carries one PROFINET interface with two ports (SCRJ + RJ45). For IRT-capable devices, check the specific ET 200SP system manual for bus adapter PROFINET conformance class.