The 6ES7232-4HD32-0XB0: The analog outputs sink up to 600 Ω when configured for current and require a load of at least 1 kΩ in voltage mode. Common-mode voltage on the output pair must not exceed 12 V. For cable runs over 100 m, shielded twisted pair is required. The front connector (ordered separately) is needed for wiring.
This module is in active current production with a lifecycle status of 'current'. No end-of-life notice is on file.