Skip to main content
Siemens 6ES7288-1SR30-0AA1 — DIN Rail Power Supplies

Siemens 6ES7288-1SR30-0AA1 S7-1200 CPU, 18 KB program, -40 t

MPN6ES7288-1SR30-0AA1

Siemens S7-1200 CPU, 6ES7288-1SR30-0AA1, 18 KB program memory, 144-byte I/O mapping, PID control, TCP/IP, PROFIBUS via CM DP, CE marked, DIN rail mount.

$182.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7288-1SR30-0AA1 key specifications
ParameterValue
TypeHardware clock, no battery backup
InterfaceRS 485 (max. 187.5 kbps)
Type of memoryDDR
Type of input voltageDC
Test voltage at air discharge8 kV
Test voltage at contact discharge4 kV
Current output, max.300 mA; 24 V DC Sensor Power
Inrush current, max.8.9 A; at 264 V
Current consumption, max.136 mA; At 120 V AC
Current consumption (rated value)72 mA; at 240 V AC
Interference emission via line (AC current cables)EN 61000-6-4, interference emission: Intended for use in industrial areas.
For signal "0", max. (Permissible quiescent current)1 mA

All specifications

6ES7288-1SR30-0AA1 additional specifications
ParameterValue
Power loss, max.14 W
S7 communicationYes
PROFINET IO deviceYes; I-Device since V2.5
PROFINET IO controllerYes; Since V2.4
Number of RS 485 interfaces1
Supports protocol for PROFINET IOYes; RT Controller (since FW V2.4) & I-Device (since FW V2.5)
Number of industrial ethernet interfaces1
Rail mountingYes; Standard - DIN rail
Installation altitude, max.2 000 m
Installation altitude, min.-1 000 m
Vertical installation, max.50 °C
Vertical installation, min.-20 °C
Horizontal installation, max.60 °C
Horizontal installation, min.-20 °C
Depth81 mm
Width110 mm
Height100 mm
Weight, approx.435 g
Fall height, max.0.3 m; five times, in product package
CE markYes
FBDYes
LADYes
RAMYes
STLYes
Max.70 °C
Min.-40 °C
FlashYes
Inputs144 byte; 256 bit of digital inputs & 56 words of analog inputs
RS 485Yes
TCP (IP)Yes
ForcingYes
Outputs144 byte; 256 bit of digital outputs & 56 words of analog outputs
PresentYes; Maintenance free, RTC requires 7 days.
120 v ACYes
230 v ACYes
IsolatedYes; Transformer isolated, 1,500V AC
PROFIBUSYes; Via CM DP module
As clientYes
As serverYes
SupportedYes
Backup time7 d
Memory size18 kbyte; Program memory
AutocrossingYes
Inputs, max.128 byte; Per device
Outputs, max.128 byte; Per device
Updating time4 ms; The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.
For signal "0"5 V DC at 1 mA
For signal "1"15 V DC at 2.5 mA
PID controllerYes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops
Shielded, max.500 m
AutonegotiationYes
ParameterizableYes; 6 Single phase: 5 HSCs at 200 kHz; 1 HSCs at 30 kHz 4 A/B phase: 3 HSCs at 100 kHz; 1 HSC at 20 kHz
"0" to "1", max.10 ms; max.
"1" to "0", max.10 ms; max.
RJ 45 (Ethernet)Yes
Rated value24 V
Unshielded, max.150 m
Micro memory cardYes; microSDHC Card (optional)
Source (sink input)Yes
Number of counters6
On lamp load, max.30 W; 30 W with DC, 200 W with AC
Up to 40 °C, max.18
At "0" to "1", max.12.8 ms
At "0" to "1", min.0.2 ms
Programming packageSTEP 7 Micro/WIN SMART
For signal "1", typ.4 mA
Deviation per day, max.120 s; within 120s/month at 25 °C
Number of pulse outputs3
Number of relay outputs8
Status (control variable)Yes
Storage (transport, max.)1 080 hPa
Storage (transport, min.)660 hPa
Transmission rate, max.100 Mbit/s
For bit operations, typ.150 ns; / instruction
Number of digital inputs18
For word operations, typ.1.2 µs; / instruction
Number of digital outputs12; Relays
With resistive load, max.2 A
Hardware clock (real-time)Yes
Memory available for user data12 kbyte
Permissible range, lower limit47 Hz
Permissible range, upper limit63 Hz
For backplane bus (5 v DC), max.1.4 A; max. 5 V DC for EM bus
For floating point arithmetic, typ.3.6 µs; / instruction
Number of connectable IO devices, max.8
Automatic detection of transmission rateYes; 10/100 Mbit/s
Limit class a, for use in industrial areasYes; EN 61000-6-4, interference emission: Intended for use in industrial areas.
Operation at 25 °C without condensation, max.95 %
Of the pulse outputs, with resistive load, max.1 Hz
Of which inputs usable for technological functions6; HSC (High Speed Counting)

Product details

CPU with integrated I/O and fieldbus

The Siemens 6ES7288-1SR30-0AA1 is an S7-1200 CPU with 18 kbyte program memory, 144 bytes each of digital and analog input/output mapping. It supports LAD, FBD, STL, and RAM programming, and includes a real-time clock with 7-day backup. The CPU handles up to 8 PID control loops and offers 6 high-speed counters (5 at 200 kHz, 1 at 30 kHz) for single-phase, plus 4 A/B phase counters (3 at 100 kHz, 1 at 20 kHz). Communications include TCP/IP, PROFIBUS via a CM DP module, and RS485 at up to 187.5 kbps. Transformer isolation at 1500 V AC separates the logic from the field wiring.

No lifecycle status is on record for this order code. The CE mark is listed, but no UL or other agency approvals appear in the specification record.

Frequently asked questions

What programming languages does the 6ES7288-1SR30-0AA1 support?

It supports LAD (ladder), FBD (function block diagram), STL (statement list), and RAM programming.

What is the operating temperature range?

The CPU operates from -40 °C to 70 °C.

Does it have a real-time clock?

Yes, it includes a hardware clock with no battery backup. The RTC requires 7 days of power-on to maintain backup time.

What fieldbus interfaces are available?

TCP/IP is built in. PROFIBUS is supported via a CM DP module. RS485 is also present at up to 187.5 kbps.

How many PID loops can it handle?

Up to 8 PID closed-loop control loops, with continuous or binary outputs and automatic/manual mode.

What is the I/O mapping capacity?

144 bytes each for digital and analog inputs and outputs, plus 256 bits of digital I/O and 56 words of analog I/O per device.

MPN
6ES7288-1SR30-0AA1