Skip to main content
Siemens 6ES7288-1ST30-0AA1 — DIN Rail Power Supplies

Siemens 6ES7288-1ST30-0AA1 SIMATIC S7-1200 CPU, -40 to 70 °C

MPN6ES7288-1ST30-0AA1

Siemens SIMATIC S7-1200 CPU, 6ES7288-1ST30-0AA1, 18 kB program memory, 144 byte I/O, PROFINET, RS-485, -40 to 70 °C, DIN rail.

$192.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6ES7288-1ST30-0AA1 key specifications
ParameterValue
TypeHardware clock, no battery backup
InterfaceRS 485 (max. 187.5 kbps)
Type of memoryDDR
Type of input voltageDC
Test voltage at air discharge8 kV
Test voltage at contact discharge4 kV
Current output, max.300 mA; 24 V DC Sensor Power
Inrush current, max.6 A; at 28.8 V
Current consumption, max.624 mA; 24 V DC
For signal "0" residual current, max.10 µA
Interference emission via line (AC current cables)EN 61000-6-4, interference emission: Intended for use in industrial areas.
For signal "0", max. (Permissible quiescent current)1 mA

All specifications

6ES7288-1ST30-0AA1 additional specifications
ParameterValue
Power loss, max.12 W
S7 communicationYes
PROFINET IO deviceYes; I-Device since V2.5
PROFINET IO controllerYes; Since V2.4
Number of RS 485 interfaces1
Supports protocol for PROFINET IOYes; RT Controller (since FW V2.4) & I-Device (since FW V2.5)
Number of industrial ethernet interfaces1
Rail mountingYes; Standard - DIN rail
Installation altitude, max.2 000 m
Installation altitude, min.-1 000 m
Vertical installation, max.50 °C
Vertical installation, min.-20 °C
Horizontal installation, max.60 °C
Horizontal installation, min.-20 °C
Depth81 mm
Width110 mm
Height100 mm
Weight, approx.375 g
Fall height, max.0.3 m; five times, in product package
CE markYes
FBDYes
LADYes
RAMYes
STLYes
Max.70 °C
Min.-40 °C
FlashYes
Inputs144 byte; 256 bit of digital inputs & 56 words of analog inputs
RS 485Yes
TCP (IP)Yes
ForcingYes
Outputs144 byte; 256 bit of digital outputs & 56 words of analog outputs
PresentYes; Maintenance free, RTC requires 7 days.
IsolatedYes; Transformer isolated, 1,500V AC
PROFIBUSYes; Via CM DP module
As clientYes
As serverYes
SupportedYes
Backup time7 d
Memory size18 kbyte; Program memory
AutocrossingYes
Inputs, max.128 byte; Per device
Outputs, max.128 byte; Per device
Updating time4 ms; The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.
For signal "0"I0.0 to I0.3 < 1 V DC; I0.4 to I2.7 < 5 V DC
For signal "1"I0.0 to I0.3 > 4V; I0.4 to I2.7 > 15V
PID controllerYes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops
Shielded, max.500 m; 50m shielded for HSC inputs
AutonegotiationYes
ParameterizableYes; 6 Single phase: 5 HSCs at 200 kHz; 1 HSCs at 30 kHz 4 A/B phase: 3 HSCs at 100 kHz; 1 HSC at 20 kHz
"0" to "1", max.3 µs; of the standard outputs, max. 3 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 1 µs
"1" to "0", max.200 µs; of the standard outputs, max. 200 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 50 µs
RJ 45 (Ethernet)Yes
Rated value24 V
Unshielded, max.300 m; for technological functions: No
Micro memory cardYes; microSDHC Card (optional)
Source (sink input)Yes
Number of counters6
On lamp load, max.5 W
Up to 40 °C, max.18
At "0" to "1", max.12.8 ms
At "0" to "1", min.0.2 ms
Programming packageSTEP 7 Micro/WIN SMART
For signal "1", min.20 V DC
For signal "1", typ.4 mA
Deviation per day, max.120 s; within 120s/month at 25 °C
Number of pulse outputs3
Number of relay outputs0
Status (control variable)Yes
Storage (transport, max.)1 080 hPa
Storage (transport, min.)660 hPa
Transmission rate, max.100 Mbit/s
For bit operations, typ.150 ns; / instruction
Number of digital inputs18
For word operations, typ.1.2 µs; / instruction
Number of digital outputs12
With resistive load, max.0.5 A
For signal "1" rated value0.5 A
Hardware clock (real-time)Yes
Of which High-Speed outputs3; 100 kHz Pulse Train Output
Memory available for user data12 kbyte
For backplane bus (5 v DC), max.1.4 A; max. 5 V DC for EM bus
For floating point arithmetic, typ.3.6 µs; / instruction
Permissible range, lower limit20.4 V
Permissible range, upper limit28.8 V
Number of connectable IO devices, max.8
Automatic detection of transmission rateYes; 10/100 Mbit/s
Limit class a, for use in industrial areasYes; EN 61000-6-4, interference emission: Intended for use in industrial areas.
Operation at 25 °C without condensation, max.95 %
Of the pulse outputs, with resistive load, max.100 kHz
Of which inputs usable for technological functions6; HSC (High Speed Counting)

Product details

The 6ES7288-1ST30-0AA1 is a CPU with 144 bytes each for inputs and outputs, mapped as 256 bits of digital plus 56 words of analog per side. It programs in LAD, FBD, and STL — so whatever your in-house standard is, this CPU speaks it. The 18 kB program memory is tight for a multi-axis line but fine for a standalone station or a pump skid. Built-in PID control handles up to 8 loops, with continuous or binary outputs and auto/manual bumpless transfer. That covers most single-loop temperature, pressure, or flow applications without an extra controller card.

Tough enough for the route

Transformer-isolated power supply, 1,500 V AC isolation. Mounts on standard DIN rail. Snap on and wire the terminals.

Communications and fieldbus

Comes with PROFINET onboard — acts as both client and server, with auto-crossing and auto-negotiation. Minimum update time is 4 ms, which is quick enough for most I/O scans but not for high-speed motion. If you need PROFIBUS, add a CM DP module. RS-485 port runs at up to 187.5 kbps for Modbus RTU or USS drives. Shielded cable maxes out at 500 m, but drop that to 50 m if you're using the high-speed counter inputs — those need a short leash to keep noise out.

CE marked for the European market. No UL or CSA listing in the evidence.

Frequently asked questions

What is the temperature range for this CPU?

Rated for -40 °C to 70 °C ambient. That's wide enough for outdoor enclosures, unheated warehouses, or hot manufacturing floors.

Does it have built-in PID control?

Yes, with up to 8 loops. It supports continuous and binary outputs, auto/manual mode, and bumpless transfer — enough for most single-loop process applications.

What communications are onboard?

PROFINET (client/server, auto-crossing) and RS-485 (up to 187.5 kbps). PROFIBUS requires an add-on CM DP module.

How does it compare to the 6ES7223-1BL32-0XB0?

The 6ES7223-1BL32-0XB0 is a different form factor — it's a combination digital I/O module, not a CPU. It won't drop into the same slot; you'd need a separate CPU plus that module. The 6ES7288-1ST30-0AA1 is a standalone CPU with its own I/O mapping.

MPN
6ES7288-1ST30-0AA1