Skip to main content
Siemens 6ES7322-1BP50-0AA0 — Digital Output Modules

Siemens 6ES7322-1BP50-0AA0 64-DO, 24V 0.3A, EOL

MPN6ES7322-1BP50-0AA0
End of Life

Siemens S7-300 digital output module, 64DO, 24 V DC, 0.3 A per channel, electronic short-circuit protection, EOL.

$951.23 – $1,568.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7322-1BP50-0AA0 — Outputs
ParameterValue
Digital outputs64
6ES7322-1BP50-0AA0 — Electrical
ParameterValue
Rated value (DC)24 V
Output current, resistive load, max.100 Hz
Output current at signal "1" (rated)0.3 A
Output current, max. per circuit / per module0.36 A
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)20.4 V
Output voltage at signal "1" (min.)M+ (0.5 V)
Output current up to 60 °C, max.1.2 A
Current consumption from backplane bus (5 V DC), max.100 mA
Power dissipation (typ.)6 W
Inductive shutdown voltage clampM+ (45 V)
Load resistance, upper limit10 kΩ
Load resistance, lower limit80 Ω
Isolation between channelsNo
Isolation between channels and backplane busYes; Optocoupler
Isolation, channels in groups of16
Isolation test voltage500 V DC
6ES7322-1BP50-0AA0 — Protection & Diagnostics
ParameterValue
Short-circuit protectionYes; Electronic
Diagnostics functionNo
Diagnostic alarmNo
Short-circuit detectionNo
Wire-break detectionNo
Redundant load controlYes
Output can drive a digital inputYes
6ES7322-1BP50-0AA0 — Performance
ParameterValue
Output switching delay 0 to 1, max.450 µs
Output switching delay 1 to 0, max.450 µs
Switching frequency, inductive load, max.0.5 Hz
Switching frequency, lamp load, max.10 Hz
6ES7322-1BP50-0AA0 — Mechanical & Connection
ParameterValue
Cable length, unshielded, max.600 m
Cable length, shielded, max.1 000 m
Width40 mm
Height125 mm
Depth112 mm
Weight (approx.)230 g

Product details

The Siemens 6ES7322-1BP50-0AA0 is a 64-channel digital output module for the S7-300 family, switching 24 V DC loads at a rated 0.3 A per channel. Production has ended (EOL), so any BOM line using this part now routes through independent supply channels.

Each output is rated 0.3 A at 24 V. The total module current is capped at 1.6 A, derating to 1.2 A as temperature increases. Electronic short-circuit protection is built in, but without diagnostic alarms on the module, a downstream fuse or sensor-level monitoring is your only fault indicator. Switching speed matters for the load type. Resistive loads can cycle at 100 Hz, inductive loads only at 0.5 Hz, and lamp loads at 10 Hz. If you're driving contactors or solenoids, stay below 0.5 Hz or add suppression.

Unshielded sensor cable runs up to 600 m; shielded runs up to 1 000 m. Isolation tested at 500 V DC between channels and backplane.

Frequently asked questions

What front connector does this module require?

It requires a separate front connector: cable type 6ES7392-4Bxx0-0AA0 or terminal block type 6ES7392-1xN00-0AA0.

MPN
6ES7322-1BP50-0AA0