6ES7332-5TB10-0AB0
MPN6ES7332-5TB10-0AB0
End of Life
SIMATIC DP, HART analog output, SM 332, 2 AO, 0/4 - 20 mA HART, as of HART Rev. 5.0, for ET200M with IM 153-2, 1 x 20-pole
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026
Specifications
Outputs
| Parameter | Value |
|---|---|
| Number of analog outputs | 2 |
| Output range: 0 to 20 mA | Yes |
| Output range: 4 to 20 mA | Yes |
| Output range: -20 mA to +20 mA | No |
| Load resistance, current outputs, max. | 650 Ω |
| Current output, no-load voltage, max. | 19 V |
| Inductive load, current outputs, max. | 7.5 mH |
| Cable length, shielded, max. | 400 m |
Performance
| Parameter | Value |
|---|---|
| Resolution (incl. sign, with overrange), max. | 12 bit; + sign |
| Error, current output (rel. to output range) | 0.15 % |
| Conversion time (per channel) | 40 ms |
| Settling time, resistive load | 2.5 ms |
| Settling time, inductive load | 2.5 ms |
| Settling time, capacitive load | 4 ms |
Power
| Parameter | Value |
|---|---|
| Rated value (DC) | 24 V |
| Power loss (typ.) | 3.5 W |
| Current consumption from backplane bus (5 V DC), max. | 100 mA |
| Current consumption from load voltage L+ (no load), max. | 150 mA |
| Reverse polarity protection | Yes |
Diagnostics
| Parameter | Value |
|---|---|
| Diagnostics function | Yes; Parameterizable |
| Diagnostic interrupt/alarm | Yes; Parameterizable |
| Wire-break detection (current outputs) | Yes; as of output value > 0.5 mA |
Isolation
| Parameter | Value |
|---|---|
| Isolation: channels to backplane bus | Yes |
| Isolation: between channels | Yes |
| Isolation: channels to load voltage L+ | Yes |
Environmental
| Parameter | Value |
|---|---|
| Temperature, max. | 60 °C |
Mechanical
| Parameter | Value |
|---|---|
| Front connector required | 20-pin |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
MPN
6ES7332-5TB10-0AB0