Skip to main content
Siemens 6ES7355-2SH00-0AE0 — PLC I/O & Expansion Modules

Siemens 6ES7355-2SH00-0AE0 FM 355-2S, 8 AI TC/RTD, EOL

MPN6ES7355-2SH00-0AE0
End of Life

Siemens FM 355-2S temperature control module, 6ES7355-2SH00-0AE0, 8 analog inputs, supports Pt 100 and thermocouples B/E/J/K/R/S, 24 VDC, EOL hot stage.

$768.10 – $1,872.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

6ES7355-2SH00-0AE0 — I/O
ParameterValue
Digital inputs8
Digital outputs8
Analog inputs4
6ES7355-2SH00-0AE0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
For signal "1"13 to 30V
For signal "0"-3 to +5V
Current for signal "1" (typ.)7 mA
Power loss (typ.)5.5 W
Current consumption from backplane bus (5 V DC), max.75 mA; typ. 50 mA
Current consumption from load voltage L+ (no load), max.270 mA; typ. 220 mA
Short-circuit protectionYes; Electronic
Isolation test voltage500 V DC
Isolation: between channelsNo
Isolation: channels to backplane busYes; Optocoupler
Max. cable length, shielded200 m; 50 m at 80 mV and thermocouples
Max. cable length, unshielded600 m
6ES7355-2SH00-0AE0 — Performance
ParameterValue
Resolution incl. overrange (bit, with sign), max.14 bit
ParameterizableYes
6ES7355-2SH00-0AE0 — Mechanical
ParameterValue
Height125 mm
Width80 mm
Depth120 mm
Weight (approx.)470 g

Product details

8-channel temperature controller for S7-300 racks

The Siemens 6ES7355-2SH00-0AE0 is an FM 355-2S temperature control module with 8 analog inputs, purpose-built for closed-loop temperature regulation on an S7-300 backplane. It accepts Pt 100 RTDs and thermocouple types B, E, J, K, R, and S — covering the vast majority of industrial temperature sensing from cryogenic to 1700 °C furnace work. The module draws its power from a 24 VDC supply (rated value 24 V) and dissipates up to 6.9 W, so budget that thermal load into the rack's ventilation — especially if the adjacent slots are also high-power analog or CPU modules.

Input flexibility — RTD, thermocouple, and millivolt

Each of the 8 channels can be configured for voltage (0 to +10 V), current (0 to 20 mA, 4 mA to 20 mA), or resistance measurement (240 Ω to 4 kΩ), with the thermocouple and Pt 100 ranges handled directly without external signal conditioners. The module also reads bipolar signals: -1.75 V to +11.75 V and -3.5 mA to +23.5 mA, making it usable for process transmitters that swing below zero on fault conditions. For thermocouple wiring, the maximum shielded cable run is 200 m, dropping to 50 m when using 80 mV range or thermocouple inputs — keep the cold-junction compensation reference junction close to the module for best accuracy.

Lifecycle reality — EOL hot stage

For a replacement path, evaluate the S7-1500-based temperature control modules (e.g., ET 200SP AI 8xRTD/TC) if a platform migration is feasible; otherwise, source this exact unit against your RFQ through our network.

Digital inputs accept 24 VDC signals with a '1' threshold of 13 to 30 V and typical draw of 7 mA per input. The module supports logic links and is fully parameterizable via the S7-300 configuration tool.

Frequently asked questions

Where can I buy the 6ES7355-2SH00-0AE0?

This module is sourced to order against an RFQ through our independent distribution network. Submit a request for current pricing and availability — stock positions vary as it is an EOL hot stage part.

MPN
6ES7355-2SH00-0AE0