Specifications

6ES7510-1SJ00-0AB0 — Identification
ParameterValue
Configurable from STEP 7 TIA Portal versionV13 SP1
Firmware versionV1.7
Hardware functional status (FS)FS01
6ES7510-1SJ00-0AB0 — Communication
ParameterValue
Transmission rate, max.12 Mbit/s
TCP/IP supportYes
Isochronous modeNo
6ES7510-1SJ00-0AB0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)19.2 V
Power loss (typ.)5.6 W
Reverse polarity protectionYes
6ES7510-1SJ00-0AB0 — I/O
ParameterValue
Input data area32 kbyte; All inputs are in the process image
Output data area32 kbyte; All outputs are in the process image
6ES7510-1SJ00-0AB0 — Environmental
ParameterValue
Operating temperature, horizontal install, min.0 °C
Operating temperature, horizontal install, max.60 °C
Operating temperature, vertical install, max.50 °C
Operating temperature, vertical install, min.0 °C
6ES7510-1SJ00-0AB0 — Mechanical
ParameterValue
Width100 mm
Height117 mm
Depth75 mm
TypeHardware clock

Product details

Compact failsafe CPU with integrated PROFINET

The Siemens 6ES7510-1SJ00-0AB0 is a compact failsafe CPU, 100 mm wide, with integrated PROFINET and support for FBD and LAD failsafe programming. It includes PROFIsafe for safety communication over the network, and handles up to 32 kbyte of process image for both inputs and outputs. Equipped with MRP redundancy manager/client capability (up to 50 devices in a ring) and MRPD requiring IRT, this CPU fits into high-availability topologies. On-board PID control for temperature and valves simplifies loop applications without extra modules.

DIN-rail mount, 100 mm wide fits standard enclosure. Depth 75 mm leaves room for front connectors and cable bend radius. Terminal access on the front; leave 50 mm clearance below for PROFINET patch cables. Spring-clamp screwless connections on the power supply and integrated I/O—strip 10 mm. PROFINET ports are on the left side; use standard RJ45 cables. For MRP rings, connect port 1 and port 2 to neighbours. No additional PROFINET switch needed for small rings.

Frequently asked questions

What does the failsafe capability mean for this CPU?

The CPU supports FBD and LAD programming with failsafe extensions (FBD incl. failsafe, LAD incl. failsafe) and PROFIsafe over PROFINET. You can write safety logic directly without an external fail-safe module, keeping the design compact.

Does it support MRP and IRT?

Yes, MRP as redundancy manager and/or client with up to 50 devices per ring. MRPD is supported but requires IRT.

What programming languages are available?

All standard S7-1500 languages: LAD, FBD, SCL, STL, GRAPH. FBD and LAD include failsafe variants.