Siemens 6ES7522-5HH00-0AB0 — Digital Output Modules

Siemens 6ES7522-5HH00-0AB0 S7-1500 16 Relay Output Module DQ

MPN6ES7522-5HH00-0AB0
Active

Siemens S7-1500, 6ES7522-5HH00-0AB0, digital output module, 16 relay outputs, DQ and MSO enabled, 24 V DC to 120 V DC / 24 V AC to 230 V AC, width 35 mm.

$256.54Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6ES7522-5HH00-0AB0 — Outputs
ParameterValue
Digital outputs16
Output typeRelays
6ES7522-5HH00-0AB0 — Electrical
ParameterValue
Rated value (DC)24 V
Output current, resistive load, max.2 A; see additional description in the manual
Output current at signal "1" (rated)2 A
Output current, max. per circuit / per module2 A; thermal continuous current
Total output current per module, max.32 A; see additional description in the manual
Permissible range, upper limit (DC)28.8 V
Permissible range, lower limit (DC)19.2 V
Residual current at signal "0", max.0 A
Power dissipation (typ.)5 W
Isolation between channelsNo
Isolation between channels and backplane busYes
Isolation, channels in groups of2
Isolation test voltageBetween channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)
6ES7522-5HH00-0AB0 — Protection & Diagnostics
ParameterValue
Short-circuit protectionNo
Reverse polarity protectionYes
Diagnostic alarmYes
Short-circuit detectionNo
Wire-break detectionNo
Redundant load controlYes
Output can drive a digital inputYes
6ES7522-5HH00-0AB0 — Performance
ParameterValue
Switching frequency, inductive load, max.2 A; see additional description in the manual
Switching frequency, lamp load, max.1 Hz
6ES7522-5HH00-0AB0 — Environmental
ParameterValue
Operating temperature, horizontal mount, max.60 °C
Operating temperature, horizontal mount, min.-25 °C; From FS02
6ES7522-5HH00-0AB0 — Mechanical & Connection
ParameterValue
Cable length, unshielded, max.600 m
Cable length, shielded, max.1 000 m
Width35 mm
Height147 mm
Depth129 mm
Weight (approx.)350 g

Product details

Module in the kit

The 6ES7522-5HH00-0AB0: No special accessories needed for basic rack mounting; the module occupies standard S7-1500 slot spacing. Typical power loss is 5 W.

Diagnostics in detail

DQ (diagnostics qualified) means the module generates diagnostic alarms on channel faults. MSO (maintenance support) raises maintenance interrupts. Both are active here, minimizing blind troubleshooting. A red ERROR LED and yellow MAINT LED indicate state at a glance; each output channel has a green status LED. Isolation tested at 3 100 V DC between channels and between channels and backplane bus, and 707 V DC type test between L+ and backplane bus. Cable lengths: shielded up to 1 000 m, unshielded up to 600 m.

Frequently asked questions

What does DQ mean on this module?

DQ (diagnostics qualified) is enabled, so the module can report diagnostic alarms on channel faults, simplifying fault isolation.

What does MSO mean on this module?

MSO (maintenance support) is enabled, meaning the module raises maintenance interrupts to the controller for preventive alerts.

MPN
6ES7522-5HH00-0AB0