The Siemens 6SL3210-1NE12-2UL0 is a SINAMICS G120 Power Module PM230 — the unfiltered IP20 variant in the FSA frame size, rated for 0.75 kW low overload on a 380-480 V three-phase supply. It's the drive end without a brains: this module needs a CU240B/E-2 or CU230P-2 control unit and firmware V4.4 or higher to run. No safety functions onboard — the PM230 family skips the integrated safe torque off, so if your line needs a safety-rated stop, you'll handle it externally or step up to a PM240.
What the ratings mean for fit
The 0.75 kW low-overload rating means the module delivers 0.75 kW continuously, with 150% overload for 3 seconds and 110% for 57 seconds — enough for a pump or fan start, not for a high-inertia load that needs a longer ramp. The 380-480 V three-phase input covers the common European and North American industrial voltages; the +10/-10% tolerance handles a sagging line. IP20 means it's for a clean, dry cabinet — no washdown, no dust. The FSA frame is compact at 196 x 73 x 165 mm, so it fits a small panel footprint but leaves no room for a built-in brake chopper or line filter.