SINAMICS V20 0.75 kW — what the ratings mean for a BOM line
The Siemens 6SL3210-5EE17-5UV0 is a SINAMICS V20 variable-frequency drive rated for 0.75 kW on a 380–480 VAC three-phase supply (47–63 Hz). The 150% overload capability for 60 seconds means it can handle short-duration peak loads — useful for starting a loaded conveyor or a pump with a high breakaway torque — without oversizing the drive frame. The unfiltered variant omits the internal EMC filter; if the installation must meet conducted-emission limits for a residential or light-industrial zone, an external filter belongs on the line side. Built-in I/O includes 4 digital inputs, 2 digital outputs, 2 analog inputs, and 1 analog output — enough for a basic speed/start-stop loop without an add-on module. Fieldbus is USS or Modbus RTU via the built-in RS-485 port; no PROFINET or EtherNet/IP on this order code, so plan the control-network architecture accordingly.
Panel integration — IP20 and frame size A
IP20 / UL open type means the drive is intended for a clean, dry enclosure — no washdown, no dust. Mount it inside a panel with at least the clearance specified in the manual for heat dissipation. The frame size A dimensions (150 x 90 x 145.5 mm, WxHxD) fit a standard 200 mm deep enclosure; leave 100 mm free above and below for airflow.