The 6SL3211-1NE17-7AL0 is a SINAMICS G120 Power Module PM230 rated for low-overload duty at 3 kW — meaning it delivers 150% rated current for 3 seconds, 110% for 57 seconds, then settles to 100% for 240 seconds. That duty cycle suits short-duration overloads like a conveyor start or a pump breakaway, not continuous overrunning loads. The integrated Class A filter meets EN 61800-3 first-environment limits, so it can run on a standard industrial mains without an external EMC filter. Input accepts 380-480 V 3 AC at 47-63 Hz. The power module ships as an FSA frame (238 x 126 x 171 mm) without a Control Unit — you pair it with a CU240B/E-2 or CU230P-2 running firmware V4.4 or higher. Note: this PM230 variant does not support safety functions; if your application requires STO or SS1, step up to the PM240-2.
Integration constraints
Ambient temperature range is 0 to +40 °C for low-overload operation. Above that, derate per the thermal curve in the device manual. The integrated fan draws air from the bottom and exhausts upward; leave 100 mm clearance above and below the module for airflow.