Integration constraints
The PM230 ships without a Control Unit or operating unit; the buyer must order a compatible CU240B/E-2 or CU230P-2 separately. Dimensions are 238 x 126 x 171 mm (HxWxD), FSA footprint. Ambient temperature range is 0 to +40 °C for low-overload operation. Because the module is unfiltered, expect conducted emissions at the line input that may require an external line reactor or EMC filter for installations subject to IEC 61800-3 Category C2 or C3 limits. The IP20 rating means no conduit seals or gaskets — the enclosure provides the environmental seal.