Active production — what it means for procurement
The 6SL3220-2YH62-0CF0: The product class is C: manufactured/produced to order, which means it is not held as off-the-shelf stock. Lead time and pricing are confirmed at RFQ against the specific BOM quantity.
450 kW rating and overload profile — sizing for pump/fan duty
Rated power is 450 kW with an overload capability of 135% for 3 seconds or 110% for 60 seconds, and 100% for 240 seconds. This profile is typical for variable-torque loads like centrifugal pumps and fans where short-duration overloads occur during start-up or surge conditions. Input supply is 3-phase 500-690 V AC +10%/-20%, 47-63 Hz — the wide voltage tolerance covers 525 V, 600 V, and 690 V nominal grids common in industrial and infrastructure installations. The EMC filter is category C3, suitable for industrial environments with a dedicated ground connection.
Frame FSH, IP20, and fieldbus — panel integration notes
The Basic Operator Panel (BOP) is included for local parameter access and commissioning without a separate HMI. Integrated fieldbus is PROFINET-PN and Ethernet IP — dual-protocol support simplifies connection to Siemens S7 controllers or Rockwell/Allen-Bradley PLCs on the same network segment. No additional communication module is required.
Compliance documentation — RoHS, REACH, export
RoHS compliant since 11 March 2020. REACH Article 33 declaration: lead (CAS 7439-92-1) present above 0.1% w/w — this is a standard disclosure for drives with lead-bearing solder joints or components; it does not restrict use under EU REACH. Export Control Regulations: AL N / ECCN 3A999A — no special export license required for most destinations, but 3A999A covers certain industrial equipment with performance parameters; confirm with your trade compliance team for re-export to restricted countries.