Skip to main content
Siemens 6SL3220-3YE36-0AB0 — AC Drive (VFD) 480V

Siemens 6SL3220-3YE36-0AB0 SINAMICS G120X VFD, 37 kW, FSD

MPN6SL3220-3YE36-0AB0
Active

Siemens SINAMICS G120X AC drive, 37 kW rated power, 380-480 V 3-phase, frame size FSD, IP20, with integrated MODBUS RTU and BACnet MS/TP, radio interference suppression filter C2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6SL3220-3YE36-0AB0 — Specifications
ParameterValue
Group codeR220
Product group4R52
Product classB: return restricted, please contact your Siemens partner/contact
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : N
Compliance with the substance restrictions according to RoHS directiveSince: 01-07-06

Product details

37 kW pump and fan drive with BACnet and MODBUS

The 6SL3220-3YE36-0AB0: It ships with an integrated radio interference suppression filter for category C2, which means it meets conducted emission limits for industrial power networks without an external filter in most installations. The drive includes an Intelligent Operator Panel and supports MODBUS RTU, BACnet MS/TP, and USS protocols natively — no additional communication module needed for building management system integration.

Panel integration and environmental limits

Frame size FSD with IP20 / UL open type protection — designed for enclosure mounting where the panel provides the environmental seal; the drive itself is touch-safe but not rated for washdown or dust ingress. Rated for ambient temperatures from -20 to +45 °C without derating; above 45 °C the output current must be reduced per the standard SINAMICS derating curve, which matters for enclosures with limited airflow. Packaging dimensions are 305 x 545 x 430 mm — plan the panel layout and gland plate clearance for the FSD footprint before cutting the backplate.

Lifecycle and compliance documentation

RoHS compliant since July 2006 and REACH Article 33 duty-to-inform documentation is available — required for EU market BOM declarations and customer compliance requests. Export Control Classification is AL: N / ECCN: N — no special export licensing required for most destinations, but confirm with your trade compliance team for end-use restrictions.

Frequently asked questions

What fieldbus protocols does this drive support?

The 6SL3220-3YE36-0AB0 has integrated MODBUS RTU, BACnet MS/TP, and USS protocols. No additional communication module is required for these fieldbuses.

What is the overload rating on this SINAMICS G120X drive?

Rated for 110% overload for 60 seconds and 100% for 240 seconds at 37 kW. This suits variable-torque loads like pumps and fans where peak demand is short-lived.

MPN
6SL3220-3YE36-0AB0