Skip to main content
Siemens 6SL3220-3YH28-0UP0 — AC Drives (VFD)

Siemens 6SL3220-3YH28-0UP0 SINAMICS G120X VFD, 15 kW

MPN6SL3220-3YH28-0UP0
Active

Siemens SINAMICS G120X AC drive, 6SL3220-3YH28-0UP0, 15 kW, 500-690 V 3AC, FSD frame size, IP20, PROFIBUS DP, unfiltered, with Intelligent Operator Panel.

StockContact for availability
Lead time1-2 Weeks wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-3YH28-0UP0 — Identification
ParameterValue
Product familyOrdering Data Overview

Other specifications

6SL3220-3YH28-0UP0 — Other specifications
ParameterValue
Group codeR220
Product group4R52
Product classB: return restricted, please contact your Siemens partner/contact
Export control regulationsAL : N / ECCN : N
Compliance with the substance restrictions according to RoHS directiveSince: 01-07-06

Product details

15 kW at 500-690 V — the high-voltage pump-and-fan drive

The Siemens 6SL3220-3YH28-0UP0 is a SINAMICS G120X variable frequency drive rated for 15 kW continuous output on a 500-690 V three-phase supply, ±10% tolerance, 47-63 Hz. This puts it squarely in the high-voltage segment — think 690 V industrial networks common in European process plants, mining conveyors, and marine auxiliary systems where a 400 V drive would need a step-up transformer. It delivers 110% overload for 60 seconds and 100% for 240 seconds, so it handles the starting torque of a centrifugal pump or fan without tripping, but it is not rated for the constant-torque overload profile a conveyor or extruder would demand. The overload duty is the spec that decides fit here, not the nameplate kW.

Frame FSD, IP20, unfiltered — panel integration constraints

The drive ships in frame size FSD with IP20 / UL open-type protection. That means it is intended for a clean, dry electrical enclosure — no washdown, no dust-laden air. The unfiltered variant lacks an internal EMC filter, so the installer must budget for an external line reactor or sine-wave filter if the installation must meet EN 61800-3 Category C2 or C3 conducted emissions limits. The packaging footprint is 305 x 545 x 430 mm — plan the backplate real estate and the gland plate entry accordingly. The drive includes an Intelligent Operator Panel (IOP) for local parameterisation and diagnostics, plus an integrated PROFIBUS DP fieldbus interface. No IO expansion module is included — if you need additional digital or analogue I/O beyond what the G120X base unit provides, that is a separate order line.

Active lifecycle — no LTB watch needed

The product class is flagged as return-restricted (class B), meaning Siemens controls the return channel — not a concern for new procurement, but something to note if you are stocking a spare for a line that cannot afford downtime. RoHS compliance dates from July 2006, and REACH Article 33 information is available on request. For a BOM freeze or a panel-builder project, this drive is a safe line item — no imminent replacement cycle, no cross-reference to chase. The export control classification is AL: N / ECCN: N, so it ships without an export licence under most regimes.

Frequently asked questions

What is the group code and product group for 6SL3220-3YH28-0UP0?

The group code is R220 and the product group is 4R52. These are Siemens internal classification codes used for ordering data and catalogue navigation.

What compliance documentation is available for this drive?

The drive is RoHS compliant since 01 July 2006, and REACH Article 33 candidate list information is available. Export control classification is AL: N / ECCN: N.

MPN
6SL3220-3YH28-0UP0