Siemens 7SJ6231-5EB02-1FG0/FF,,F — General Purpose Relays

Siemens 7SJ6231-5EB02-1FG0/FF,,F SIPROTEC 4 Protection Relay

MPN7SJ6231-5EB02-1FG0/FF,,F

Siemens SIPROTEC 4 7SJ62 Multifunction Protection Relay, order code 7SJ6231-5EB02-1FG0/FF,F, panel flush mount, screw-type terminals, 110-250 VDC / 115-230 VAC auxiliary supply, 1/3 19" housing 7XP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

7SJ6231-5EB02-1FG0/FF,,F — Specifications
ParameterValue
Housing7XP20
Designation0 = ARC,fault locator,synchro-check (without)
Product typeSIPROTEC 4 7SJ62 Multifunction Protection Relay
Unit versionE = For panel flush mounting, screw-type terminal (direct connection/ring-type cable lugs)
Housing, inputs,outputs3 = 1/3 19’’, 4xU, 4xI,8BI,8BO, 1 live status-contact
System interface (PortB)0 = No system interface
Service interface (Port c)2 = DIGSI/modem/RTD box, electrical RS485
Measuring (faulty recording)1 = Fault recording
Measuring inputs(3xV/4xV,4xI)1 = Iph=1A, Ie=1A (min. = 0.05A) Position 15 only with A,C,E,G
Rated auxiliary voltage(power supply,indication voltage)5 = 110 to 250VDC, 115to230VAC,thres hold binary input 88VDC
Region-specific default settings (function versions and language settings)B = Region World, 50/60 Hz, IEC/ANSI, language: English (GB), selectable

Product details

The 7SJ6231-5EB02-1FG0/FF,,F: The 7SJ6231-5EB02-1FG0/FF,F is a Siemens SIPROTEC 4 7SJ62 multifunction protection relay in the 1/3 19" housing 7XP20. It's built for panel flush mounting with screw-type terminals that accept direct connection or ring-type cable lugs. The auxiliary supply covers 110 to 250 VDC or 115 to 230 VAC, with a binary input threshold at 88 VDC. This variant carries four voltage and four current measurement inputs, eight binary inputs, eight binary outputs, and one live status contact. The current inputs are rated for 1 A phase and 1 A earth (minimum 0.05 A). Fault recording is included, and the service interface is DIGSI/modem/RTD box over electrical RS485.

The 110-250 VDC / 115-230 VAC auxiliary supply range is the first thing to check against your control power. The binary input threshold of 88 VDC means the relay won't pick up on a weak DC bus; plan your trip and alarm circuits accordingly. The 1 A CT inputs (minimum 0.05 A) suit standard protection-class current transformers — if your installation uses 5 A secondaries, this isn't the right variant. Region-specific defaults are set to World, 50/60 Hz, IEC/ANSI, with English (GB) language selectable. That covers most global installations without needing a firmware reflash. The housing 7XP20 is a 1/3 19" sub-rack form factor — it takes up one-third of a standard 19" rack width, so plan your panel layout accordingly.

Frequently asked questions

What auxiliary voltage does this relay require?

The rated auxiliary voltage is 110 to 250 VDC or 115 to 230 VAC. The binary input threshold is 88 VDC.

What is the housing and mounting style?

The housing is 7XP20, a 1/3 19" sub-rack. The unit version is for panel flush mounting with screw-type terminals (direct connection or ring-type cable lugs).

What are the current transformer input ratings?

The measuring inputs are 1 A phase and 1 A earth, with a minimum detectable current of 0.05 A.

MPN
7SJ6231-5EB02-1FG0/FF,,F