Siemens MVL661.15-1.0
MPNMVL661.15-1.0
SIEH Electronically Operated Valves
$1,153.35 – $1,792.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
| Parameter | Value |
|---|---|
| Operating voltage | DC 20...30 V |
| Position feedback signal u voltage | DC 0/2…10 V; load resistance ≥ 500 ? |
| Current | DC 0/4…20 mA; load resistance ≤ 500 ? |
| Current draw | 0.5 A / 2 A (max.) |
| Power supply | Extra low-voltage only (SELV, PELV) |
| Rated apparent power SNA | 32 VA (for selecting the transformer) |
| Typical power consumption pmed | 12 W |
| Frequency | 45...65 Hz |
| Max. cable length | See «Connection type», page 5 |
| Cable entry glands | 3 x Ø 17 mm (for M16) |
| Min. wire cross-section | 0.75 mm2 |
| No function (ZC not wired) | Positioning signal Y active |
All specifications+16 ▾
| Parameter | Value |
|---|---|
| Shipping weight | 6 kg |
| DC 24 | Operating voltage : DC 20...30 VCurrent draw : 0.5 A / 2 A (max.) |
| Standby | < 1 W (valve closed) |
| Manufacturer | Siemens |
| Nonlinearity | Accuracy ± 3 % full scale |
| Required fuse | 1.6...4 A (slow) |
| Input impedance | 22 k? |
| Control signal y | DC 0/2...10 V or DC 0/4...20 mA |
| Positioning time | < 1 s |
| Stroke detection | Inductive |
| Estimated lead time | 1-10 Working Days. |
| Impedance DC 0 2...10 | 100 k? / 5nF |
| Impedance DC 0 4...20 | 240 ? / 5nF |
| Open valve (ZC connected to g) | > AC 6 V; > DC 5 V |
| External supply line protection | Fuse slow max. 10 A or Circuit breaker max. 13 A Characteristic B, C, D according to EN 60898 or Power source with current limitation of max. 10 A |
| Close valve (ZC connected to g0) | < AC 1 V; <DC 0.8 V |
MPN