What the EOL status means for your BOM line
The FX1N-60MT-001: No official successor order code is listed in the manufacturer's records. For a BOM that requires this exact model, the only path is the surplus and broker market — availability and pricing are confirmed at RFQ time, not before.
I/O configuration and power supply
This PLC provides 36 input points (X000–X177, octal numbering) and supports up to 128 output relay points (Y000–Y177) when expansion is used. The input format is sink-type with a rated voltage of AC100–240V at 50/60Hz. The power supply includes a 250V 3.15A fuse and draws an inrush current of up to 30A for 5ms at AC100V or 50A at AC200V. Grounding must be Class D (ground resistance 100Ω or less) per the specification.
Program memory and real-time clock
The program memory holds up to 8000 steps including file registers, with a comment capacity also at 8000 steps. A built-in real-time clock tracks dates from 1980 to 2079 with leap-year correction and a typical monthly deviation of ±45 seconds at 25°C. The clock is backed by a large-capacitor that charges in 30 minutes and holds the time for 10 days; an optional battery can extend backup. The PLC includes 256 special auxiliary relays (M8000–M8255), 384 general-purpose auxiliary relays (M0–M383), and 128 pointers for JUMP and CALL branch instructions (P0–P127). Timers include 200 on-delay 100ms timers (T0–T199, 0.1–3276.7 seconds) and 46-point 10ms timers (T200–T245, 0.01–327.67 seconds).
Environmental and mechanical limits
The FX1N-60MT-001 is rated for use in atmospheres free of corrosive gases, flammable gases, and conductive dust. It should not be used in pressurized environments above 2000m or under conditions exceeding atmospheric pressure, as failure risk increases.