Skip to main content
Siemens 3RK1308-0BB00-0CP0

Siemens SIMATIC 3RK1308-0BB00-0CP0 Reversing Starter, 55 kA

MPN 3RK1308-0BB00-0CP0
Active

Siemens SIMATIC reversing starter, 3RK1308-0BB00-0CP0, 1 A at 40 °C, 55 kA SCCR at 400 V, PROFINET/PROFIBUS DP, pluggable base unit.

$209.55 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RK1308-0BB00-0CP0 specifications
ParameterValue
Mountingpluggable in BaseUnit
Depth150 mm
Width30 mm
Height142 mm
Trip classCLASS OFF / 5 / 10 adjustable

Product details

The Siemens SIMATIC 3RK1308-0BB00-0CP0 is a reversing motor starter — a single module that handles forward/reverse control of a three-phase motor without external contactor interlocking. It's rated 1 A at 40 °C and carries a 55 kA short-circuit breaking capacity at both 400 V and 500 V, so it can be placed on a high-fault panel bus without needing upstream current-limiting fuses for the starter itself. The trip class is adjustable: CLASS OFF, 5, or 10, which means you can match the thermal overload curve to the motor's starting profile — useful when the same module is used across different load types like pumps and conveyors.

Fieldbus and integration

This module supports PROFINET and PROFIBUS DP natively. Input data is 4 bytes, output data 2 bytes. It plugs into a base unit; width is 30 mm, depth 150 mm.

Operating temperature range is -25 to +60 °C with derating above 40 °C; storage and transport range is -40 to +70 °C. Vibration resistance is 15 mm at 6 Hz, then 2 g up to 500 Hz; shock resistance is 6 g for 11 ms. The safe state is load circuit open, meaning on fault or communication loss the outputs drop out and the motor coasts or brakes per the external circuit.

Supply voltage and load considerations

Supply voltage range is 20.4 V to 28.8 V. Minimum load is 50% of the smallest adjustable rated current. ON-delay is 20 ms; OFF-delay is 35 to 50 ms.

MPN