Skip to main content
Siemens 5SL3520-7

Siemens 5SL3520-7 SENTRON MCB, 1P+N C-curve 20 A, 4.5 kA

MPN 5SL3520-7

Siemens SENTRON 5SL3520-7, miniature circuit breaker, 1P+N, C-curve, 20 A, 4.5 kA (EN 60898), 230 V AC, 2 MW, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL3520-7 specifications
ParameterValue
Poles2
IP ratingIP20
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

It breaks fault currents up to 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — the EN figure governs residential and light commercial distribution boards; the IEC figure applies when the breaker is used in industrial panel applications where the standard calls for 60947-2 coordination. Installation depth is 70 mm. Mounting position is unrestricted.

C-curve and real-world load

Power loss is 2.2 W per pole in hot operating state at rated current. In a multi-breaker panel, that heat adds up — derating calculations should account for it if the enclosure is sealed and ambient runs above 40 °C. The breaker itself is rated for -40 to 75 °C ambient, so the limit is the panel's internal temperature rise, not the component.

IP20 with connected conductors means the terminals are finger-safe only when wired; the busbar entry points are not protected against dust ingress, so the breaker belongs inside an enclosure, not exposed on the plant floor. Energy limitation class 3 means the let-through energy on a fault is limited enough to protect downstream equipment within the breaker's rated breaking capacity.

MPN
5SL3520-7