Skip to main content
Siemens 5SL4220-8CC

Siemens 5SL4220-8CC SENTRON MCB, 2-Pole D 20 A, 10 kA

MPN 5SL4220-8CC
Active

Siemens SENTRON 5SL4220-8CC miniature circuit breaker, 2-pole, D tripping characteristic, 20 A rated current, 10 kA breaking capacity per EN 60898 at 400 V AC, 2 modular width units.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL4220-8CC specifications
ParameterValue
Poles2
IP ratingIP20
Depth76 mm
Width36 mm
Height90 mm

Product details

Siemens 5SL4220-8CC SENTRON MCB — 2-Pole D-Curve 20 A

The Siemens 5SL4220-8CC is a SENTRON miniature circuit breaker (MCB) with a D tripping characteristic, rated 20 A at 400 V AC and a 10 kA breaking capacity per EN 60898. It is a 2-pole design occupying 2 modular width units (36 mm wide) on a DIN rail, with an installation depth of 70 mm and overall depth of 76 mm.

The D-curve's magnetic trip threshold (10–20× In) is the key selection parameter: if you are protecting a fixed-speed motor start or a power supply with a large input capacitor bank, this breaker holds through the inrush that a C-curve (5–10× In) would trip.

Integration Notes

Supplementary devices (shunt trip, auxiliary contacts, alarm switch) can be added on the right side via the product extension feature.

MPN