Skip to main content
Siemens 5SL6116-6

Siemens 5SL6116-6 SENTRON MCB, 1P, B Curve, 16A, 6kA

MPN 5SL6116-6
Active

Siemens SENTRON 5SL6116-6, miniature circuit breaker, 1-pole, B characteristic, 16 A, 6 kA per EN 60898, 1 MW unit, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL6116-6 specifications
ParameterValue
Poles1
IP ratingIP20
Depth76 mm
Width18 mm
Height90 mm
Energy limitation class3

Product details

Siemens 5SL6116-6 SENTRON MCB — 16 A, B Curve, 1-Pole

Rated AC supply voltage is 400 V for multi-phase operation, 250 V single-phase, at 50/60 Hz. Maximum DC rating is 72 V.

Mounting position is unrestricted. The sealable design allows padlocking the toggle in the OFF position for lockout/tagout.

The 6 kA breaking capacity according to EN 60898 and IEC 60947-2 means this breaker safely interrupts a fault up to 6,000 A without welding its contacts or causing a flashover. For a 16 A final circuit in a domestic or light commercial board with a typical prospective fault level of 3–4 kA, that gives adequate headroom. Energy limitation class 3 means it lets through less energy than class 1 or 2 breakers, reducing stress on downstream wiring. The 10,000 mechanical operating cycles typical service life is standard for an MCB in this class.

MPN