Its C-curve tripping characteristic means it holds up to 5–10× rated current momentarily — suited for motor and transformer inrush where a B-curve would nuisance-trip, but not for the high-inrush of heavy drives (that would want a D-curve). Rated for 400 V AC multi-phase and single-phase operation, with a maximum of 440 V AC — so it fits standard 400 V three-phase and 230/400 V single-phase distribution, but not 480 V line-to-line systems. Maximum DC voltage is 72 V. Installation depth is 70 mm; housing depth is 76 mm.

Siemens 5SN6250-8CP MCB 5SN 2-pole C-curve 400V 6kA/10kA
MPN 5SN6250-8CP
Siemens SENTRON MCB 5SN, 2-pole, C-curve, 400 V AC, 72 V DC, 6 kA (EN 60898) / 10 kA (IEC 60947-2), 2 modular width units, 36 mm wide.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Poles | 2 |
| Depth | 76 mm |
| Width | 36 mm |
| Height | 90 mm |
Product details
5SN6250-8CP Datasheet
MPN