Skip to main content
Siemens 5SU1354-6KK13

Siemens 5SU1354-6KK13 SENTRON RCBO, 13 A, B Curve, 10 kA

MPN 5SU1354-6KK13
Active

Siemens SENTRON 5SU1354-6KK13 RCBO, 1P+N, 13 A rated at 30 °C, B tripping characteristic, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, 2 MW units wide, 77 mm depth.

$67.04 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1354-6KK13 specifications
ParameterValue
Poles2
Depth77 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

It protects a single-phase final subcircuit against earth leakage and overload/short-circuit in one DIN-rail module. Rated 13 A at 30 °C ambient, it carries a 10 kA breaking capacity per EN 60898 and 20 kA per IEC 60947-2, so it can clear faults up to those levels without upstream coordination failure.

Temperature derating — the real continuous current

Inside a warm enclosure the available current drops: 12.48 A at 40 °C, 11.96 A at 50 °C, 11.31 A at 60 °C, and 10.01 A at 70 °C. If your panel runs at 50 °C ambient, size the downstream load for 11.96 A continuous, not the label 13 A.

Panel integration — DIN-rail fit and wiring

The IP20 rating applies once the distribution board is installed with conductors connected; it is not a standalone outdoor rating.

The higher 20 kA figure means this RCBO can be applied in industrial sub-distribution where fault currents reach 20 kA, provided the upstream device coordinates. The 4 kV rated surge voltage resistance (impulse withstand) covers typical mains transients in TN and TT systems.

MPN