Skip to main content
Siemens 5SU1374-8DK81

Siemens 5SU1374-8DK81 SENTRON RCBO, Type B+ 30mA, D-Curve 10

MPN 5SU1374-8DK81
Active

Siemens SENTRON 5SU1374-8DK81, RCBO, 4-pole, Type B+ residual current 30 mA, D tripping characteristic, 100 A at 30 °C, 10 kA breaking capacity.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1374-8DK81 specifications
ParameterValue
Poles4
Depth77 mm
Width198 mm
Height90 mm
Energy limitation class3

Product details

The Siemens 5SU1374-8DK81 is a 4-pole RCBO from the SENTRON series, combining overcurrent protection with residual current detection in a single modular device. It carries a Type B+ residual current sensitivity of 30 mA and a D tripping characteristic for the overcurrent element, rated at 100 A at 30 °C ambient.

The 100 A rating holds at 30 °C; at 40 °C it derates to 92.5 A, at 50 °C to 85 A, and at 60 °C to 77 A.

Residual current type and application

Type B+ residual current protection detects AC, pulsating DC, smooth DC, and high-frequency AC fault currents up to 1 kHz. This makes it suitable for circuits with variable-speed drives, UPS systems, EV chargers, and other equipment that can generate mixed-frequency or DC residual currents. The D tripping characteristic handles high inrush loads like motors and transformers without nuisance tripping.

MPN
5SU1374-8DK81