Skip to main content
Siemens 5SV9313-7NK20

Siemens 5SV9313-7NK20 SENTRON RCD Circuit Breaker, 20 A C

MPN 5SV9313-7NK20

Siemens SENTRON 5SV9313-7NK20, RCD-operated circuit breaker, 1P+N, 20 A, C characteristic, 4.5 kA, Type A, 18 mm width.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SV9313-7NK20 specifications
ParameterValue
Poles2
Temp operating max40 °C
Temp operating min-25 °C
Depth77 mm
Width18 mm
Height90 mm

Product details

It protects a single-phase AC circuit against overload, short-circuit, and earth leakage, with a Type A fault-current sensor that catches pulsating DC residual currents (common from rectifiers, VFDs, and switching supplies) as well as sinusoidal AC faults.

In a domestic or light commercial distribution board with a typical upstream fuse or MCB rated higher, this holds. The C curve means magnetic trip occurs at 5 to 10 times rated current (100–200 A for this 20 A unit), so it's sized for circuits with motor or transformer inrush. Temperature derating is published: 20 A at 30 °C, 19 A at 40 °C, 18 A at 50 °C, 17.4 A at 55 °C. If your enclosure runs hot, size the load accordingly — the 40 °C figure is the one most panels see. The 18 mm width (1 width unit) fits standard SENTRON distribution boards. Touch protection is built in (IP20 with conductors connected).

MPN
5SV9313-7NK20