Skip to main content
Siemens 4EU3632-0ME08-1BA0

Siemens SIDAC 4EU3632-0ME08-1BA0 Filter Reactor, 249 A, 400

MPN 4EU3632-0ME08-1BA0

Siemens SIDAC filter reactor, 3-phase, 249 A rated / 276 A max, 400 V AC, 50 Hz, 150 kvar, IP00, flat connector / screw-type terminals.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

4EU3632-0ME08-1BA0 specifications
ParameterValue
IP ratingIP00
Depth0.227 m
Width0.35 m
Height0.321 m

Product details

The Siemens SIDAC 4EU3632-0ME08-1BA0 is a 3-phase filter reactor rated for 249 A continuous (276 A maximum) at 400 V AC, 50 Hz. It delivers 150 kvar of reactive power and carries a relative throttling factor of 5.67% with an inductance of 0.0002 H. The resonant frequency is 210 Hz, which means it's tuned to suppress the 5th harmonic — the dominant harmonic from 6-pulse drives — while staying clear of the fundamental.

The 249 A rated current at 400 V AC matches the line-side current of a typical 160 kW to 200 kW 6-pulse drive (depending on drive efficiency and load profile). The 5.67% impedance is the standard value for most drive line reactors — enough to limit harmonic distortion and reduce DC-bus ripple without dropping too much voltage under load. Thermal class H (180 °C) means the winding insulation can handle sustained high ambient temperatures inside a crowded cabinet; the 40 °C ambient rating is conservative, but you'll need to derate if the panel ambient pushes above that.

IP00 means no enclosure — this is a bare reactor meant for installation inside a metal cabinet where the cabinet itself provides the touch protection. The main circuit connects via flat connectors or screw-type terminals, which is typical for this current range: flat busbars for the high-current path, screw terminals for the control wiring. Mounting dimensions are 0.35 m wide, 0.321 m tall, and 0.227 m deep — plan for a cabinet depth of at least 300 mm to leave room for busbars and cable bending radius behind the reactor.

MPN
4EU3632-0ME08-1BA0