Integration notes
Supply voltage range 20.4–28.8 V DC — a standard 24 V panel bus works, and the low-end tolerance catches brownout conditions without nuisance dropout. Input current per channel is 5 mA, a standard load for most PLC-sourced 24 V. Output current maximum 0.5 A per point; total package limit isn't stated, so parallel outputs only for the same load if you can guarantee inrush stays under 0.5 A per pin. IP20 enclosure — mount inside a cabinet with at least a basic dirt/drip shield. Modbus TCP over the Industrial Ethernet port (no fieldbus variant here). Delay time configurable 0.1–32 ms, useful for debouncing a noisy sensor or aligning with slow valve actuation.