Skip to main content
ABB 1SDA068116R1 — Molded Case Circuit Breakers (MCCB)

1SDA068116R1 ABB XT4N 160 MA 52, 52A motor protection breake

MPN1SDA068116R1

ABB XT4N 160 MA 52, 1SDA068116R1, motor protection circuit breaker, 52 A In, adjustable short-circuit trip 260…520 A, 3-pole, 690 V.

$433.00Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

1SDA068116R1 — Ratings
ParameterValue
Number of poles3 poles
1SDA068116R1 — Other specifications
ParameterValue
In52
Iu160
DimensionsXT4
TypeXT4N 160 MA 52 Im=260...520 3p F F
Weight2.1 Kg
Trip unitsMA
Product typeMotor Protection Circuit Breakers
Dimensions (LxWxH)8.25cm x 10.5cm x 16cm
Current52 A
Voltage690 V
Rated frequency50 / 60 Hz

Product details

The 1SDA068116R1 is an ABB XT4N motor protection circuit breaker with a magnetic-only (MA) trip unit. It's rated 52 A continuous (In) on a 160 A frame (Iu), giving you a compact 3-pole device for motor branch circuits where you want fast short-circuit protection but handle overload separately with an external relay. The adjustable short-circuit trip range of 260…520 A (4–10x In) lets you dial it in without swapping components — handy when the motor inrush data lands somewhere between catalogue values. Rated voltage 690 V at 50/60 Hz covers most industrial supply systems.

Sizing a coordinated pair

Since the MA trip lacks thermal overload, you'll need an external overload relay (e.g., ABB T series or electronic equivalent) wired between the breaker and the motor contactor. The adjustable Im setting lets you match the motor's locked-rotor current without oversizing the protection — useful when you're replacing an existing breaker on a line and want to avoid changing the contactor or cable.

Frequently asked questions

What is the rated current (In) of 1SDA068116R1?

The continuous rated current In is 52 A. This is the current the breaker can carry without tripping under normal conditions.

What is the frame size (Iu) of this breaker?

The frame rating Iu is 160 A, which determines the physical size and the maximum short-circuit capacity of the XT4 platform.

MPN
1SDA068116R1