Specifications

1SDA068124R1 — Electrical
ParameterValue
Rated current (In)100 A
Number of poles3 poles
Rated voltage (Ur)690 V
Rated uninterrupted current (Iu)160
Rated frequency50 / 60 Hz
1SDA068124R1 — Protection
ParameterValue
Trip unitEkip LS/I
1SDA068124R1 — Mechanical
ParameterValue
Dimensions (L x W x H)8.25cm x 10.5cm x 16cm
Weight2.1 Kg
1SDA068124R1 — Identification
ParameterValue
Type designationXT4N 160 Ekip LS/I In=100A 3p F F
Product type designationDistribution Circuit Breakers
SizeXT4
1SDA068124R1 — Other specifications
ParameterValue
In100

Product details

Frame and ratings — what In=100A and Iu=160A mean for your panel

The 1SDA068124R1 is an ABB XT4N 160 molded case circuit breaker with a rated current (In) of 100 A and a frame rating (Iu) of 160 A. The In value is the continuous current the breaker is calibrated to carry without tripping; the Iu is the maximum current the XT4 frame can handle when fitted with a higher-rated trip unit. For this specific unit, the Ekip LS/I electronic trip is set for 100 A, so the breaker protects downstream conductors and loads at that level, while the frame itself has headroom up to 160 A if you ever swap the trip block. Rated voltage is 690 V AC at 50/60 Hz, covering standard 400/480 V distribution panels globally. The 3-pole configuration handles three-phase circuits — common for motor control centers, distribution boards, and feeder protection in commercial and industrial installations.

Ekip LS/I trip unit — protection curve breakdown

The Ekip LS/I is an electronic trip unit offering long-time (L), short-time (S), and instantaneous (I) protection. Long-time delay handles overloads with an adjustable thermal memory; short-time delay coordinates with downstream breakers for selective coordination; instantaneous clears hard faults within a few milliseconds. This makes the breaker suitable for both feeder and main applications where you need adjustable time-current curves, not just a fixed thermal-magnetic response.

Frequently asked questions

What is the difference between In=100A and Iu=160A on this breaker?

In (100 A) is the rated current the trip unit is calibrated for — the breaker will trip at 100 A continuous load. Iu (160 A) is the maximum current the XT4 frame can carry if fitted with a different trip unit. This means the breaker is set for 100 A protection now, but the frame has 60 A of headroom for future re-rating by swapping the Ekip LS/I trip block.

What compliance documentation does ABB provide for 1SDA068124R1?

ABB provides a declaration of conformity to IEC 60947-2 for molded case circuit breakers, along with CE marking for the European market. RoHS and REACH compliance statements are available on request. The breaker carries UL/CSA certification for North American installations — verify the specific UL file number with the order documentation.