Frame and trip unit for distribution protection
The ABB 1SDA068134R1 is an XT4N 160 moulded-case circuit breaker (MCCB) with a 160 A frame (Iu) and a 100 A continuous rated current (In), fitted with the Ekip LSI electronic trip unit. The 3-pole configuration and 690 V rated voltage make it suitable for three-phase distribution panels in 400 V and 480 V systems, with headroom for 690 V applications.
Ekip LSI trip unit — adjustable protection curves
The Ekip LSI electronic trip unit provides independent adjustment of long-time (L), short-time (S), and instantaneous (I) protection thresholds. This allows the panel builder to coordinate selectivity with downstream breakers and upstream transformers without changing the breaker frame. The LSI curve is field-adjustable via the trip unit's rotary dials or through the Ekip Connect software for documented settings. Rated frequency is 50/60 Hz, covering both global mains standards without derating. The 690 V rated voltage (Ur) ensures the breaker can be applied on 400 V, 480 V, and 690 V systems while maintaining the interrupting capacity specified for the XT4N frame.