The screw terminals accept rigid cable up to 95 mm² (main circuit) and 2.5 mm² (control circuit), with a control-circuit torque spec of 0.5 N·m. It includes a bypass contactor inside — the run, fault, bypass, and overload signal relays (all present) give you dry contacts for the PLC without extra interposing relays.

ABB 1SFA895007R7000 PST72 Soft Starter, 72 A In-Line, 37 kW
ABB PST72 soft starter, 1SFA895007R7000, 72 A in-line (124 A inside delta), 37 kW at 400 V, 24 V DC control, 0-120 s ramp time, 0-10 V analog output, screw terminals, IP10 main terminals.
Specifications
| Parameter | Value |
|---|---|
| Terminal type | Screw Terminals |
| Product main type | PST72 |
| Voltage | Main Circuit 400 ... 690 V AC |
| Initial voltage during start | 30 ... 70 % |
| Step down voltage special ramp | 100 ... 30 % |
| Rated control circuit voltage | DC Operation 24 V |
| Current limit function | 1.5 ... 7xIe |
| Starting capacity at maximum rated current ie | 3xIe for 15s |
| Rated operational current - In-Line connection | 72 A |
| Rated operational current - inside delta connection | 124 A |
| Rated operational power - In-Line connection | (400 V) 37 kW |
| Rated operational power - inside delta connection | at 400 V 59 kW |
All specifications
| Parameter | Value |
|---|---|
| Rated frequency | 50/60 Hz |
| IP rating | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
| Protocol | FiledBusPlug(Standard) |
| Switch for inside delta connection | Yes |
| Material compliance (Conflict minerals reporting template) | 9AKK108467A5658 |
| Ramp time | 0 ... 120 second [unit of time] |
| Analog outputs | 0...10 volts |
| Run signal relay | Yes |
| Tightening torque | Control Circuit 0.5 N·m |
| Fault signal relay | Yes |
| Overload protection | Build-in electronic overload protection |
| By-pass signal relay | Yes |
| Overload signal relay | Yes |
| Ambient air temperature | Operation 0 ... +50 °C |
| Service factor percentage | 115 % |
| Object classification code | Q |
| Signal indication fault | Red |
| Integrated electronic overload | Yes |
| Connecting capacity main circuit | Rigid 1 x 10 ... 95 mm² |
| Connecting capacity supply circuit | Rigid 1 x 2.5 |
| Signal indication protection | Yellow |
| Connecting capacity control circuit | Rigid 1 x 2.5 mm² |
| Popular downloads (Instructions and manuals) | 1SFC132003M0201 |
| Popular downloads (Data sheet, technical information) | 1SFC132005C0201 |
Product details
Frequently asked questions
What is the ramp time on the 1SFA895007R7000?
The ramp time is adjustable from 0 to 120 seconds, covering soft-start profiles from near-instant to a gradual 2-minute acceleration.
What communication does the 1SFA895007R7000 support?
It uses a standard FieldBusPlug — a modular connector that accepts optional fieldbus adapters (PROFIBUS, DeviceNet, etc.) via a plug-in module, not a built-in protocol.
Where can I buy 1SFA895007R7000?
It's available to order through independent distribution channels. Submit an RFQ for current pricing and lead time — availability is confirmed at quote time.
What compliance documentation does ABB provide for this soft starter?
ABB provides a Conflict Minerals Reporting Template (CMRT) under document 9AKK108467A5658. The product is classified as B2B small equipment (WEEE Category 5) with no RoHS declaration needed per the evidence.