Skip to main content
ABB 1SFA898119R7000 — Soft Starters

ABB 1SFA898119R7000 PSTX840 Soft Starter, 208-600V AC, Auto

MPN1SFA898119R7000
Active

ABB, PSTX840 series, Soft Starter, 1SFA898119R7000, 208...600 V AC, 100...250 V AC control supply, 24 V DC control circuit, 1...120 s ramp time, auto phase sequence detection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

1SFA898119R7000 key specifications
ParameterValue
Terminal typeMain Circuit: Bars
Product main typePSTX840
Voltage208 ... 600 V AC
Initial voltage during start10 ... 99 V
Step down voltage special ramp100 ... 10 %
Rated control supply voltage100 ... 250 V AC
Rated control circuit voltage24 V DC
Technical UL (CSA, maximum operating voltage UL, CSA)Main Circuit 600 V
Current limit function1.5 ... 7.5 xle
Starting capacity at maximum rated current ie4xIe for 10s
Rated operational current - In-Line connection840 A
Rated operational current - inside delta connection1455 A

All specifications

1SFA898119R7000 additional specifications
ParameterValue
Technical UL (CSA, horsepower rating UL, CSA)(200 ... 208 V AC) Three Phase 300 Hp
Rated operational power - In-Line connection(230 V) 250 kW
Rated operational power - inside delta connectionat 230 V 450 kW
Rated frequency50/60 Hz
IP ratingacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
ProtocolModbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Switch for inside delta connectionYes
Popular downloads (CAD dimensional drawing)2CDC001079B0201
Material compliance (Toxic substances control act - TSCA)2CMT2023-006524
Material compliance (Conflict minerals reporting template)9AKK108467A5658
Technical UL (CSA, tightening torque UL, CSA)Main Circuit 398.3
FunctionAuto phase sequence detection
Ramp time1 ... 120 second [unit of time]
Analog outputs0...10 V, 0...20 mA, 4...20 mA
Warning detailsCurrent imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning
Run signal relayYes
Tightening torqueMain Circuit 45 N·m
Fault signal relayYes
Overload protectionBuilt-in electronic overload protection
Protection functionBypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection
By-pass signal relayYes
Overload signal relayYes
Ambient air temperatureOperation -25 ... +60 °C
Service factor percentage100 %
Object classification codeQ
Popular downloads (EPLAN data)9AAC185674_EPLAN
Signal indication faultRed
Integrated electronic overloadYes
Signal indication running rGreen
Connecting capacity supply circuitRigid 1 x 2.5
IDEA granular category code4740 >> Soft starter
Signal indication protectionYellow
Connecting capacity control circuitRigid 1 x 2.5 mm²
Popular downloads (Instructions and manuals)1SFC132428M0201
Popular downloads (Data sheet, technical information)1SFC132012C0201
Popular Downloads/Instructions and manuals (Part 2)1SFC132081M0201
Popular Downloads/Instructions and manuals (Part 3)1SFC132060M0201

Product details

The ABB 1SFA898119R7000 is a PSTX840 soft starter with auto phase sequence detection built in — it verifies phase rotation on power-up and protects against reverse-running motors. Rated for 208...600 V AC operational voltage, with a control supply of 100...250 V AC and a separate 24 V DC control circuit. Ramp time is adjustable from 1 to 120 seconds, giving you fine control over acceleration for pumps, conveyors, or compressors.

Main circuit terminals are bars with a tightening torque of 45 N·m — expect a bolted bus-bar connection, not spring terminals. The control circuit accepts rigid 1 x 2.5 mm² wire. Degree of protection at the main terminals is IP00, so the unit needs to be inside an enclosure for washdown or dusty environments.

Communication options are extensive: Modbus-RTU, Modbus-TCP, Ethernet/IP, EtherCAT, DeviceNet, CANopen, Profibus, Profinet, BACnet-IP, and BACnet-MSTP — covers nearly every industrial network. Built-in electronic overload protection eliminates the need for a separate overload relay. Protection functions include current imbalance, earth fault, locked rotor, phase reversal, under/over voltage, and PTC/PT-100 motor thermal sensing.

Frequently asked questions

Where can I buy 1SFA898119R7000 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 1SFA898119R7000's listed function?

Its primary function is auto phase sequence detection — it checks phase rotation before the motor starts and can prevent reverse-running damage.

What is 1SFA898119R7000's listed ramp time?

Ramp time is adjustable from 1 to 120 seconds, letting you tailor acceleration for different load types.

What compliance documentation does this brand provide for 1SFA898119R7000?

RoHS compliant following EU Directive 2011/65/EU and Amendment 2015/863. WEEE category 5 (Small Equipment). CAD dimensional drawing and EPLAN data are available as popular downloads.

MPN
1SFA898119R7000