Skip to main content
ABB 1SFA898206R7000 — Soft Starters

ABB 1SFA898206R7000 PSTX60 Soft Starter, 208-690V AC, 50/60

MPN1SFA898206R7000
Active

ABB PSTX60 soft starter, 1SFA898206R7000, auto phase sequence detection, ramp time 1–120 s, 208–690 V AC, 50/60 Hz, multi-protocol communication.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

1SFA898206R7000 key specifications
ParameterValue
Terminal typeCable Clamp
Product main typePSTX60
Voltage208 ... 690 V AC
Initial voltage during start10 ... 99 %
Step down voltage special ramp100 ... 10 %
Rated control supply voltage100 ... 250 V AC
Rated control circuit voltage24 V DC
Technical UL (CSA, maximum operating voltage UL, CSA)Main Circuit 690 V
Current limit function1.5 ... 7.5 xle
Starting capacity at maximum rated current ie4xIe for 10s
Rated operational current - In-Line connection60 A
Rated operational current - inside delta connection105 A

All specifications

1SFA898206R7000 additional specifications
ParameterValue
Technical UL (CSA, horsepower rating UL, CSA)(200 ... 208 V AC) Three Phase 20 Hp
Rated operational power - In-Line connection(230 V) 15 kW
Rated operational power - inside delta connectionat 230 V 30 kW
Rated frequency50/60 Hz
IP ratingacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
ProtocolModbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Switch for inside delta connectionYes
Material compliance (SCIP)d1eab0cb-c4c6-4233-8fa0-1a9d9a9b7de8 China
Popular downloads (CAD dimensional drawing)2CDC001079B0201
Material compliance (Toxic substances control act - TSCA)2CMT2023-006524
Material compliance (Conflict minerals reporting template)9AKK108467A5658
Technical UL (CSA, tightening torque UL, CSA)Main Circuit 70.8
FunctionAuto phase sequence detection
Ramp time1 ... 120 second [unit of time]
Analog outputs0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA
Warning detailsCurrent imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning
Run signal relayYes
Tightening torqueMain Circuit 8 N·m
Fault signal relayYes
Overload protectionBuilt-in electronic overload protection
Protection functionBypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection
By-pass signal relayYes
Overload signal relayYes
Ambient air temperatureOperation -25 ... +60 °C
Service factor percentage100 %
Object classification codeQ
Popular downloads (EPLAN data)9AAC181162_EPLAN
Signal indication faultRed
Integrated electronic overloadYes
Connecting capacity main circuitHole Diameter 8.5 mm
Signal indication running rGreen
Connecting capacity supply circuitRigid 1 x 2.5
IDEA granular category code4740 >> Soft starter
Signal indication protectionYellow
Connecting capacity control circuitRigid 1 x 2.5 mm²
Popular downloads (Instructions and manuals)1SFC132428M0201
Popular downloads (Data sheet, technical information)1SFC132012C0201
Popular Downloads/Instructions and manuals (Part 2)1SFC132081M0201
Popular Downloads/Instructions and manuals (Part 3)1SFC132060M0201

Product details

What this PSTX60 soft starter does on the line

The ABB 1SFA898206R7000 is a PSTX60 soft starter with built-in auto phase sequence detection — it checks incoming phase rotation before the motor starts, so a reversed-phase jam on a conveyor or pump is caught at commissioning, not after the contactor pulls in. Ramp time is adjustable from 1 to 120 seconds, which covers soft-start profiles from a quick kick on a low-inertia fan to a long acceleration on a loaded conveyor or centrifuge. Rated operational voltage spans 208 to 690 V AC at 50/60 Hz, so it fits standard low-voltage networks from 230 V to 690 V without a transformer tap.

Protection set — what it watches and why

Built-in electronic overload protection replaces a separate thermal overload relay, and the protection list includes ground fault, locked rotor, phase reversal, voltage imbalance, current underload, and too-long start time — all configurable through the HMI or fieldbus. Warning outputs cover the same conditions plus motor runtime limit, faulty fan, EOL, and thyristor overload — so the maintenance team gets an early alert before a trip shuts the line.

Frequently asked questions

What is 1SFA898206R7000's listed function?

Its primary function is auto phase sequence detection — it verifies incoming phase rotation before the motor starts, preventing reverse-rotation damage on pumps, conveyors, and compressors.

What is the ramp time range on this soft starter?

The ramp time is adjustable from 1 to 120 seconds, covering soft-start profiles from quick starts on low-inertia loads to long acceleration on high-inertia or loaded conveyors.

What compliance documentation does ABB provide for this part?

RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863. SCIP material compliance is registered under number d1eab0cb-c4c6-4233-8fa0-1a9d9a9b7de8 for China. WEEE category is 5 (Small Equipment) and classification is B2B.

MPN
1SFA898206R7000