Skip to main content
ABB 1SFA898219R7000 — Soft Starters

ABB 1SFA898219R7000 PSTX840 Soft Starter, 208-690V AC, Auto

MPN1SFA898219R7000
Active

ABB, PSTX840 series, soft starter, 1SFA898219R7000, 208...690 V AC, 50/60 Hz, auto phase sequence detection, ramp 1...120 s, multi-protocol fieldbus.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

1SFA898219R7000 key specifications
ParameterValue
Terminal typeMain Circuit: Bars
Product main typePSTX840
Voltage208 ... 690 V AC
Initial voltage during start10 ... 99 %
Step down voltage special ramp100 ... 10 %
Rated control supply voltage100 ... 250 V AC
Rated control circuit voltage24 V DC
Technical UL (CSA, maximum operating voltage UL, CSA)Main Circuit 690 V
Current limit function1.5 ... 7.5 xle
Starting capacity at maximum rated current ie4xIe for 10s
Rated operational current - In-Line connection840 A
Rated operational current - inside delta connection1455 A

All specifications

1SFA898219R7000 additional specifications
ParameterValue
Technical UL (CSA, horsepower rating UL, CSA)(200 ... 208 V AC) Three Phase 300 Hp
Rated operational power - In-Line connection(230 V) 250 kW
Rated operational power - inside delta connectionat 230 V 450 kW
Rated frequency50/60 Hz
IP ratingacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
ProtocolModbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Switch for inside delta connectionYes
Popular downloads (CAD dimensional drawing)2CDC001079B0201
Material compliance (Toxic substances control act - TSCA)2CMT2023-006524
Material compliance (Conflict minerals reporting template)9AKK108467A5658
Technical UL (CSA, tightening torque UL, CSA)Main Circuit 398.3
FunctionAuto phase sequence detection
Ramp time1 ... 120 second [unit of time]
Analog outputs0...10 V, 0...20 mA, 4...20 mA
Warning detailsCurrent imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning
Run signal relayYes
Tightening torqueMain Circuit 45 N·m
Fault signal relayYes
Overload protectionBuilt-in electronic overload protection
Protection functionBypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection
By-pass signal relayYes
Overload signal relayYes
Ambient air temperatureOperation -25 ... +60 °C
Service factor percentage100 %
Object classification codeQ
Popular downloads (EPLAN data)9AAC185674_EPLAN
Signal indication faultRed
Integrated electronic overloadYes
Signal indication running rGreen
Connecting capacity supply circuitRigid 1 x 2.5
IDEA granular category code4740 >> Soft starter
Signal indication protectionYellow
Connecting capacity control circuitRigid 1 x 2.5 mm²
Popular downloads (Instructions and manuals)1SFC132428M0201
Popular downloads (Data sheet, technical information)1SFC132012C0201
Popular Downloads/Instructions and manuals (Part 2)1SFC132081M0201
Popular Downloads/Instructions and manuals (Part 3)1SFC132060M0201

Product details

Soft starter with built-in intelligence

The ABB 1SFA898219R7000 is a PSTX840 soft starter rated for 208...690 V AC at 50/60 Hz, with auto phase sequence detection that prevents the motor from starting if phase rotation is incorrect — a common commissioning gotcha that can reverse a conveyor or damage a pump. Ramp time is adjustable from 1 to 120 seconds, giving you control over acceleration profiles for high-inertia loads like fans or centrifuges. The unit integrates electronic overload protection and protection functions including earth fault, locked rotor, and voltage imbalance.

Fieldbus flexibility and analog feedback

Communication options cover Modbus-RTU, Modbus-TCP, EtherNet/IP, EtherCAT, DeviceNet, CANopen, PROFIBUS, PROFINET, BACnet-IP, and BACnet-MSTP — so it drops into just about any control architecture without a gateway. The analog outputs (0...10 V, 0...20 mA, 4...20 mA) give you a direct speed or current signal for a local meter or PLC analog card. Main circuit terminals are bars with a 45 N·m tightening torque — expect to use a torque wrench on the lug connections. Control circuit wiring accepts 1 x 2.5 mm² rigid, and the control supply is 100...250 V AC with a separate 24 V DC control circuit for the logic.

Frequently asked questions

What is the function of 1SFA898219R7000?

Its primary listed function is auto phase sequence detection — it checks that the incoming three-phase rotation matches the motor connection before starting, preventing reverse rotation on conveyors, pumps, and compressors.

What fieldbus protocols does this soft starter support?

It supports Modbus-RTU, Modbus-TCP, EtherNet/IP, EtherCAT, DeviceNet, CANopen, PROFIBUS, PROFINET, BACnet-IP, and BACnet-MSTP — ten protocols covering most major industrial networks.

MPN
1SFA898219R7000