1SFA898220R7000 key specifications
ParameterValue
Terminal typeMain Circuit: Bars
Product main typePSTX1050
Voltage208 ... 690 V AC
Initial voltage during start10 ... 99 %
Step down voltage special ramp100 ... 10 %
Rated control supply voltage100 ... 250 V AC
Rated control circuit voltage24 V DC
Technical UL (CSA, maximum operating voltage UL, CSA)Main Circuit 690 V
Current limit function1.5 ... 7.5 xle
Starting capacity at maximum rated current ie4xIe for 10s
Rated operational current - In-Line connection1050 A
Rated operational current - inside delta connection1810 A

All specifications

1SFA898220R7000 additional specifications
ParameterValue
Technical UL (CSA, horsepower rating UL, CSA)(200 ... 208 V AC) Three Phase 400 Hp
Rated operational power - In-Line connection(230 V) 315 kW
Rated operational power - inside delta connectionat 230 V 500 kW
Rated frequency50/60 Hz
IP ratingacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
ProtocolModbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Switch for inside delta connectionYes
Popular downloads (CAD dimensional drawing)2CDC001079B0201
Material compliance (Toxic substances control act - TSCA)2CMT2023-006524
Material compliance (Conflict minerals reporting template)9AKK108467A5658
Technical UL (CSA, tightening torque UL, CSA)Main Circuit 398.3
FunctionAuto phase sequence detection
Ramp time1 ... 120 second [unit of time]
Analog outputs0...10 V, 0...20 mA, 4...20 mA
Warning detailsCurrent imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning
Run signal relayYes
Tightening torqueMain Circuit 45 N·m
Fault signal relayYes
Overload protectionBuilt-in electronic overload protection
Protection functionBypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection
By-pass signal relayYes
Overload signal relayYes
Ambient air temperatureOperation -25 ... +60 °C
Service factor percentage100 %
Object classification codeQ
Popular downloads (EPLAN data)9AAC185675_EPLAN
Signal indication faultRed
Integrated electronic overloadYes
Signal indication running rGreen
Connecting capacity supply circuitRigid 1 x 2.5
IDEA granular category code4740 >> Soft starter
Signal indication protectionYellow
Connecting capacity control circuitRigid 1 x 2.5 mm²
Popular downloads (Instructions and manuals)1SFC132428M0201
Popular downloads (Data sheet, technical information)1SFC132012C0201
Popular Downloads/Instructions and manuals (Part 2)1SFC132081M0201
Popular Downloads/Instructions and manuals (Part 3)1SFC132060M0201

Product details

The ABB 1SFA898220R7000 is a PSTX1050 soft starter with auto phase sequence detection, sized for three-phase motors on 208-690 V AC supplies. Ramp time is adjustable from 1 to 120 seconds, giving you control over acceleration profiles for conveyors, pumps, or fans. The built-in electronic overload protection eliminates the need for a separate overload relay, saving panel space and wiring.

This soft starter supports Modbus-RTU, Modbus-TCP, Ethernet-IP, EtherCAT, DeviceNet, CANopen, Profibus, Profinet, BACnet-IP, and BACnet-MSTP — covering essentially every industrial network in common use. Analog outputs are configurable for 0-10 V, 0-20 mA, or 4-20 mA, so you can feed speed or current signals directly to a PLC analog input card without an external signal conditioner.

Protection and warnings

The PSTX1050 includes protection functions: current imbalance, current underload, earth fault, locked rotor, over/under voltage, phase reversal, and PT-100/PTC connection for motor thermal monitoring. Warning outputs cover the same conditions plus fan fault, EOL, and THD(U).

Frequently asked questions

What is 1SFA898220R7000's listed function?

The primary function is auto phase sequence detection, which automatically verifies correct phase rotation before the motor starts.

What is the ramp time range for this soft starter?

Ramp time is adjustable from 1 to 120 seconds, allowing you to match acceleration to the load characteristics.

What compliance documentation does ABB provide for 1SFA898220R7000?

RoHS compliance following EU Directive 2011/65/EU and Amendment 2015/863 is documented. WEEE category is Business To Business, Large Equipment.