The 2CCF004153R0001: The 1 A to 1.6 A overload range sets the motor full-load current window — set the dial to match the motor nameplate FLA. Class 10 tripping means the breaker will open within 10 seconds at 7.2× the current setting, which protects standard squirrel-cage induction motors during a locked-rotor start without nuisance tripping on normal acceleration. The 3-pole construction switches all three phases simultaneously, so a single-phase condition on the line side still clears the motor circuit.
Dimensions are 94.5 mm wide, 90 mm tall, and 54 mm deep — fits a standard panel-mount cutout or DIN rail. Accepts flexible conductors from 0.75 mm² up to 6 mm². IP20 rated for finger-safe installation inside an enclosure; no gland-plate sealing needed.