ABB 2CCS451001R0065 — 1-Pole MCB (DIN Rail)

ABB 2CCS451001R0065 1-Pole MCB, B Curve, 6 A, 6 kA, DIN Rail

MPN2CCS451001R0065

ABB System pro M compact, 1-pole miniature circuit breaker, B characteristic, 6 A rated current, 440 V rated insulation voltage, 6 kA breaking capacity, DIN rail mount, IP20

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

2CCS451001R0065 — Electrical & Protection
ParameterValue
Overvoltage categoryIII
2CCS451001R0065 — Mounting & Connection
ParameterValue
Width69 mm
Height89 mm
Depth94.5 mm
2CCS451001R0065 — Other specifications
ParameterValue
Poles1
IP ratingIP20
MountingDIN Rail Mount
Current6 A
Terminal contact typeScrew
Voltage440 V
Tripping characteristicsB
Rated Short-Circuit breaking capacity icn6 kA
Rated Short-Circuit breaking capacity icu6 kA

Product details

Branch-circuit protection for resistive and lighting loads

The ABB 2CCS451001R0065 is a 1-pole miniature circuit breaker with a B tripping curve, rated 6 A continuous current and a short-circuit breaking capacity of 6 kA per IEC/EN 60898-1.

DIN rail fit and enclosure clearance

Overall depth of 94.5 mm and height of 89 mm — check the enclosure door clearance, especially if a busbar or wiring duct sits in front of the breaker row.

Rated insulation voltage and overvoltage category

Rated insulation voltage is 440 V, overvoltage category III — suitable for fixed-installation distribution boards downstream of the utility meter, where transient overvoltages up to 4 kV are expected. IP20 finger-safe terminals accept screw-clamp wiring; the housing is not rated for wet or dust-laden environments.

Current production — no lifecycle concern

It is suitable for both new panel builds and replacement spares. ABB lists no direct successor — this order code remains the active version for the B-curve, 6 A, 1-pole position.

Frequently asked questions

How can I order ABB 2CCS451001R0065 or check availability?

This is a current-production part sourced through independent distribution. Submit an RFQ with your BOM quantity; pricing and lead time are confirmed at quote time. No stock-holding claim is made here.

What does the B tripping curve mean for my circuit?

The B curve trips at 3 to 5 times the 6 A rated current — so between 18 A and 30 A for a magnetic trip. This is suited for resistive loads with low inrush; for motor or transformer circuits with higher starting current, a C or D curve breaker would be a better choice.

Can ABB 2CCS451001R0065 be used for DC applications?

The evidence does not list a DC voltage rating or DC breaking capacity. This breaker is specified for AC circuits at 440 V insulation voltage. For DC branch protection, consult the ABB DC-rated MCB series.

MPN