ABB 2CCS471001R0064 — 1-Pole MCB (DIN Rail)

ABB 2CCS471001R0064 1-Pole MCB, C-Curve, 6A, 10kA

MPN2CCS471001R0064

ABB 1-pole miniature circuit breaker, C-curve, 6 A rated current, 10 kA Icn breaking capacity, 440 V insulation voltage, IP20, DIN rail mount, screw terminals.

$55.94 – $58.94Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

2CCS471001R0064 — Electrical & Protection
ParameterValue
Overvoltage categoryIII
2CCS471001R0064 — Mounting & Connection
ParameterValue
Width69 mm
Height89 mm
Depth94.5 mm
2CCS471001R0064 — Other specifications
ParameterValue
Poles1
IP ratingIP20
MountingDIN Rail Mount
Current6 A
Terminal contact typeScrew
Voltage440 V
Tripping characteristicsC
Rated Short-Circuit breaking capacity icn10 kA
Rated Short-Circuit breaking capacity icu25 kA

Product details

C-curve trip characteristic, 6 A rating

The ABB 2CCS471001R0064 is a 1-pole miniature circuit breaker (MCB) with a C-curve tripping characteristic and a 6 A rated current. The C-curve magnetic trip operates between 5 and 10 times the rated current, making it the standard choice for branch circuits feeding small motors, lighting banks, and transformers where moderate inrush currents are expected. Rated insulation voltage is 440 V, and the overvoltage category is III — this breaker is designed for fixed installation downstream of the main distribution board, not for equipment-level protection.

Breaking capacity and fault-current rating

The service breaking capacity (Icn) is 10 kA per IEC 60898 — this is the value that governs the installation's fault-current rating and the breaker's ability to clear a short-circuit and remain serviceable afterward. The ultimate breaking capacity (Icu) is 25 kA, representing the maximum fault current the breaker can interrupt once without replacement. For a panel fed from a transformer with a prospective short-circuit current below 10 kA, the Icn figure is the binding limit. Above 10 kA, the breaker still clears the fault (up to 25 kA) but must be replaced afterward.

DIN-rail form factor and panel integration

The breaker mounts on a standard DIN rail (EN 60715) and occupies a single module width of 69 mm. Depth is 94.5 mm, height is 89 mm — these dimensions fit standard distribution board enclosures without clearance issues. IP20 rated — the terminals are finger-safe but the breaker is not sealed against moisture or dust. Suitable for indoor panel environments only. Screw terminals accept field wiring with ring or fork lugs; torque values are marked on the terminal face.

Frequently asked questions

What is the breaking capacity of 2CCS471001R0064?

The service breaking capacity (Icn) is 10 kA per IEC 60898; the ultimate breaking capacity (Icu) is 25 kA. The Icn value governs the installation's fault-current rating.

What is the tripping characteristic of this ABB MCB?

C-curve — magnetic trip between 5 and 10 times the 6 A rated current. Designed for moderate inrush loads such as small motors, lighting circuits, and transformers.