Skip to main content
ABB 2CCS862001R0104 — 2-Pole MCB (DIN Rail)

2CCS862001R0104 MCB, C-curve 10A, 2-pole, 25kA Icn

MPN2CCS862001R0104

ABB High Performance Miniature Circuit Breaker, C-curve, 10 A, 2-pole, 690 V rated insulation voltage, 25 kA Icn / 50 kA Icu breaking capacity, IP20, DIN rail mount.

$214.56 – $220.11Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

2CCS862001R0104 — Protection
ParameterValue
Overvoltage categoryIV
2CCS862001R0104 — Mechanical
ParameterValue
Width54 mm
Height95 mm
Depth82.5 mm
2CCS862001R0104 — Other specifications
ParameterValue
Poles2
IP ratingIP20
MountingDIN Rail Mount
Current10 A
Terminal contact typeScrew
Voltage690 V
Tripping characteristicsC
Rated Short-Circuit breaking capacity icn25 kA
Rated Short-Circuit breaking capacity icu50 kA

Product details

The 25 kA Icn (rated short-circuit breaking capacity per IEC 60898) is the service breaking capacity for general distribution; the 50 kA Icu (ultimate breaking capacity per IEC 60947-2) is the maximum fault it can clear once and still be functional afterward. Rated insulation voltage of 690 V and overvoltage category IV mean this breaker is rated for the line side of the installation — at the service entrance or main distribution board — not just downstream subpanels. Overvoltage category IV is the highest within the IEC 60947-2 framework, covering equipment connected to the utility supply point. That makes this part suitable for main incoming feeders in 400/690 V industrial networks.

Dimensions are 54 mm wide (2-pole width, 2 x 18 mm per pole), 95 mm tall, 82.5 mm deep. The 82.5 mm depth includes the breaker body and the screw terminals — account for that when laying out the enclosure depth, especially in shallow wall-mount boxes. IP20 finger-safe terminals mean the front face is touch-safe once installed, but the breaker is not sealed against dust or moisture; it belongs inside a panel with a door.

Frequently asked questions

What is the breaking capacity of this breaker?

Rated short-circuit breaking capacity Icn is 25 kA per IEC 60898; ultimate breaking capacity Icu is 50 kA per IEC 60947-2. The 25 kA Icn is the service rating for general distribution; the 50 kA Icu is the maximum fault it can clear once.

What does the C-curve mean for this 10 A breaker?

The C-curve trips at 5 to 10 times rated current (50 to 100 A magnetic trip). It is intended for circuits with moderate inrush — small motors, transformers, capacitor banks — where a B-curve would trip on startup surge.

What is the physical size of this breaker?

Width 54 mm (2-pole, 18 mm per pole), height 95 mm, depth 82.5 mm. Mounts on 35 mm DIN rail.

MPN
2CCS862001R0104