Skip to main content
ABB 2CCS891001R0104 — 1-Pole MCB (DIN Rail)

2CCS891001R0104 MCB 1P C-curve 10A 25kA Icn, DIN rail

MPN2CCS891001R0104

ABB 2CCS891001R0104, High Performance Miniature Circuit Breaker, 1-pole, C-curve, 10 A, 690 V, IP20, DIN rail mount.

$126.30 – $132.70Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

2CCS891001R0104 — Electrical & Protection
ParameterValue
Overvoltage categoryIV
2CCS891001R0104 — Mounting & Connection
ParameterValue
Width27 mm
Height95 mm
Depth82.5 mm
2CCS891001R0104 — Other specifications
ParameterValue
Poles1
IP ratingIP20
MountingDIN Rail Mount
Current10 A
Terminal contact typeScrew
Voltage690 V
Tripping characteristicsC
Tightening torque - Screw-Type max.3.5 Nm
Rated Short-Circuit breaking capacity icn25 kA
Rated Short-Circuit breaking capacity icu36 kA

Product details

The 2CCS891001R0104 is a 1-pole miniature circuit breaker (MCB) with a C-curve trip characteristic, rated 10 A continuous current. The 25 kA rated short-circuit breaking capacity (Icn) tells you it can safely interrupt a fault up to 25 kA under standard conditions; the 36 kA ultimate breaking capacity (Icu) is the maximum it can break once and still function after. For most commercial and light industrial panelboards fed by a transformer of 400 kVA or less, 25 kA Icn is sufficient — but if your fault current study shows higher, the 36 kau Icu gives you a safety margin for the one-shot event.

The 27 mm width (1-module) means it occupies a single pole position in a distribution board — tight for retrofit where panel space is already allocated. Screw terminals accept up to 3.5 Nm torque, which is typical for 10 A branch circuits; use a torque screwdriver to avoid terminal heating. IP20 finger-safe rating means it's protected against solid objects larger than 12.5 mm (fingers) but not against moisture — install inside a panel or enclosure with a higher IP-rated door.

Voltage and overvoltage class

Rated insulation voltage of 690 V means the internal clearance and creepage distances are designed for 690 V phase-to-phase systems — common in 400/690 V industrial grids (e.g., IT systems or delta-connected supplies). Overvoltage category IV means it's rated for installation at the origin of the installation (main distribution board), where transient overvoltages are highest. That's a step above the usual Cat III for sub-distribution.

Frequently asked questions

What is the breaking capacity of this MCB?

Rated short-circuit breaking capacity Icn is 25 kA; ultimate breaking capacity Icu is 36 kA. The Icn figure governs standard duty; Icu is the one-shot maximum.

What does the C-curve mean for my application?

C-curve trips at 5 to 10 times rated current (50–100 A for this 10 A unit). It is suited for circuits with moderate inrush, such as motor starters, contactor coils, and small transformers. For purely resistive loads (heaters, lighting) a B-curve would trip faster; for heavy motor inrush a D-curve may be needed.

What is the physical size for panel layout?

Width 27 mm (1 module), height 95 mm, depth 82.5 mm. Fits standard DIN-rail enclosures; the 82.5 mm depth means it clears most 100 mm deep enclosures, but check your gland plate clearance.

MPN
2CCS891001R0104