Skip to main content
ABB 2CDS251103R0065 — 2-Pole MCB (DIN Rail)

ABB 2CDS251103R0065 S200 MCB, B Curve 6A 2-Pole, 6 kA Icn

MPN2CDS251103R0065

ABB S200 series miniature circuit breaker, B curve, 6 A, 2-pole, 440 V rated insulation voltage, 6 kA Icn / 20 kA Icu, DIN rail mount, IP20/IP40.

$405.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

2CDS251103R0065 — Protection
ParameterValue
Overvoltage categoryIII
2CDS251103R0065 — Mechanical
ParameterValue
Width35 mm
Height88 mm
Depth69 mm
2CDS251103R0065 — Other specifications
ParameterValue
Poles2
IP ratingIP20;IP40
MountingDIN Rail Mount
Current6 A
Terminal contact typeBi-Directional Cylinder Lift
Voltage440 V
Tripping characteristicsB
Tightening torque - Screw-Type max.2.8 Nm
Rated Short-Circuit breaking capacity icn6 kA
Rated Short-Circuit breaking capacity icu20 kA

Product details

ABB S200 2CDS251103R0065 — 6 A B-Curve MCB for Panel Protection

The Icn rating of 6 kA is the service breaking capacity per IEC 60898 — the level the breaker can safely interrupt repeatedly. The Icu rating of 20 kA is the ultimate breaking capacity per IEC 60947-2, a one-shot fault clearance figure that gives headroom for high-fault locations near transformers. For a 6 A B-curve MCB, the 20 kA Icu means it can be applied downstream of a larger upstream device without cascading failure, provided the prospective short-circuit current at its installation point does not exceed that value.

Panel Integration and Enclosure Fit

The 2-pole width is 35 mm (one module per pole), height 88 mm, depth 69 mm. The IP20 enclosure rating means finger-safe terminals when installed in a panel; IP40 applies to the front face, protecting against tools and small wires entering the actuator slot. The bi-directional cylinder-lift terminal accepts up to 2.8 Nm tightening torque, compatible with standard screwdrivers and ferruled conductors.

Frequently asked questions

What is the breaking capacity of 2CDS251103R0065?

The service breaking capacity Icn is 6 kA per IEC 60898; the ultimate breaking capacity Icu is 20 kA per IEC 60947-2, giving fault-clearing headroom for high-fault locations.

What does the B tripping curve mean for this breaker?

The B curve trips at 3 to 5 times rated current (18–30 A for this 6 A unit), designed for resistive and general-purpose loads with low inrush — lighting, socket circuits, control transformers.

Where can I buy 2CDS251103R0065?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
2CDS251103R0065